FMS Commissioning Tips & Tricks
st
Programming 1 point If no separate fuel/air ratio is to be set for the ignition point Aids
(ignition load point) (selectable via parameter 4= 0 or 2), proceed as described here.
________________________________________________________
For safety reasons
"Setting” mode permits direct access to the control elements
with the burner running. It is therefore essential to follow the
safety rules laid down by the burner manufacturer.
"Setting mode” with the system running must only be
undertaken by trained and experienced personnel, whilst
keeping a constant watch on the system.
________________________________________________________
The first point entered after clearing the memory is always the
ignition load point. This need not be the lowest load point, it is
possible to enter ones lower than this.
At least 1 point must be entered in order to form a new curve.
A subsequent addition up to 20 points is possible at any time,
see "Adding points” on page 47.
________________________________________________________
Mode selector switch (2) to "Setting”
- "EI” appears in the middle of the display A6
Selector switch (1) to "Load rating”
Run to ignition load point by means of channel 1 switch (4) D1, D2,
D5
Selector switch (1) to "Set point”
Switch (4) up or down
until system is optimally adjusted at ignition load point
- control element reacts
- display changes E2
Selector switch (1) to "Actual value feedback”
! - Value of the external feedback (with continuous output)
! is displayed
! - with three-point step channel the same value as in
! "set point” position is displayed B1, C1
!
On FMS 5: Selector switch (1) to "Channel 5 display”
- set point and actual value feedback are displayed.
Switch (4) (channel 2) up or down
until channel 5 is optimally adjusted
Wait until feedback has stopped
Programming with burner running Press Acceptance (3)
(i.e. pre-ventilation has been carried - "Really ignite?” appears on display
out previously without ________________________________________________________
programmed point): By operating the switch the ignition point setting can be
corrected again.