FMS Fault Correction General Faults (A)
Aids
A14 ___________________________________________________________________
Fault 106 In checking the redundant parameters an error was identified
___________________________________________________________________
If data were provided via PC interface:
Read in parameter again
if this is not possible:
select said parameter
check value displayed and if necessary amend
___________________________________________________________________
In order to restore the parameter, a change must be made. If the correct value
is displayed, adjust by one digit and change back again.
___________________________________________________________________
Should several parameters be defective, repeat as necessary.
___________________________________________________________________
If the parameter is not included in your release level, an EEPROM must
be requested from LAMTEC.
___________________________________________________________________
_____________________________________________________________________________________________________
A15
Fault 105 On attempting to store the curve in the EPROM an error was identified.
140
Repeat programming
if necessary, change EEPROM, see A12
_____________________________________________________________________________________________________
A16
It was attempted to store or add The curve already contains 20 points. It is not possible to add any more.
a point, but there appear Only individual load points can be altered (recognisable from the flashing
to be “> 20 points" figure after the load rating). Otherwise a new curve must be entered
via "Clear memory".
or
if a fuel change occurred after "Clear memory" the old curve is reactivated.
Run load down and clear memory again.
Selector switch (2) to "Clear memory"
Press Acceptance (3)
_____________________________________________________________________________________________________
A17
The software version number The unit supplied possibly did not correspond to the order.
displayed does not match the Consult LAMTEC. (For address see back cover of this booklet) or since the
number on the configuration sticker. time of delivery the program EPROM has been changed and the new
checksums were not noted.
_____________________________________________________________________________________________________
A18
The running text Voltage off and back on
"Recessed selector switch defective!
Automatic activated!" appears If fault appears again
Change front panel
___________________________________________________________________
Further fault-free operation is possible. In the event of a defective selector
switch, however, it may be that the "Setting" mode can no longer be
selected.
___________________________________________________________________