Seasonal energy performance ratio
Annual electricity consumption
Parameters at full load and reference ambient temperature at rating point A
Rated refrigeration capacity P
A
42,30 kW
Rated power input D
A
15,02 kW
Rated energy efficiency ratio EER
DC,A
2,80 [-]
Parameters at rating point B
Rated refrigeration capacity P
B
39,48 kW
Rated power input D
B
10,28 kW
Rated energy efficiency ratio EER
DC,B
3,82 [-]
Parameters at rating point C
Rated refrigeration capacity P
C
36,66 kW
Rated power input D
C
7,23 kW
Rated energy efficiency ratio EER
DC,C
5,05 [-]
Parameters at rating point D
Rated refrigeration capacity P
D
33,84 kW
Rated power input D
D
5,06 kW
Rated energy efficiency ratio EER
DC,D
6,65 [-]
Degradation co-efficient chillers C
dc
0,90 [-]
GWP of the refrigerant 2088
kg CO
2 eq
(100 years)