30
Seasonal energy performance ratio
Annual electricity consumption
Parameters at full load and
reference ambient temperature at rating point A
Rated refrigeration capacity P
A
55,10 kW
Rated power input D
A
20,49 kW
Rated energy efficiency ratio EER
DC,A
2,67 [-]
Parameters at rating point B
Rated refrigeration capacity P
B
51,43 kW
Rated power input D
B
13,91 kW
Rated energy efficiency ratio EER
DC,B
3,67 [-]
Parameters at rating point C
Rated refrigeration capacity P
C
47,75 kW
Rated power input D
C
9,77 kW
Rated energy efficiency ratio EER
DC,C
4,85 [-]
Parameters at rating point D
Rated refrigeration capacity P
D
44,08 kW
Rated power input D
D
6,86 kW
Rated energy efficiency ratio EER
DC,D
6,38 [-]
Degradation co-efficient chillers C
dc
0,90 [-]
GWP of the refrigerant 2088
kg CO
2 eq
(100 years)