KEOR MULTIPLUG
600 VA - 800 VA
EN
4.3 Shutdown
1. Press and hold the ON/OFF button until the blue led turns off.
2. The UPS stops powering the back-up outlets.
3. Unplug the UPS from the mains power supply socket to stop powering also the overvoltage
protected outlets.
4.4 LED and Alarm Indicators
NORMAL MODE/
BATTERY MODE LED
ALARM
LED
ALARM UPS STATUS
Steady OFF OFF The UPS is operating in normal mode
LED blinking every 3
seconds
OFF OFF
UPS operating in battery mode with
battery status 40%-100%
LED blinking every 3
seconds
OFF
1 beep every 10
seconds
UPS operating in battery mode with
battery status 20%-40%
LED blinking every 2
seconds
OFF
1 beep every 2
seconds
UPS operating in battery mode with
battery status <20%
Steady OFF Intermittent Overload in normal mode
OFF Steady
Continuously
sounding
UPS shutdown due to prolonged
overload
Steady Steady
1 beep every 10
seconds
Battery fault
OFF Steady
Continuously
sounding
UPS fault (other than overload)