KEOR SP
Manuel d’installation • Installation manual

Table of Contents

Questions and Answers

  • C
    christopher43Aug 10, 2025
    What to do if my LEGRAND UPS works on battery even with mains power?
    • T
      Taylor RobertsonAug 11, 2025
      If your LEGRAND UPS is running on battery even when mains power is available, there could be two reasons. First, the UPS fuse might have blown; replace it with a new one (T5AL250V). Second, the mains power supply socket might not be providing power; try plugging the UPS into another socket. If it works, have the initial socket checked by a qualified electrician.
  • T
    Thomas ColeAug 17, 2025
    What to do if my LEGRAND KEOR SP 1000 alarm LED is on?
    • D
      Dawn MackAug 17, 2025
      If the alarm LED on your LEGRAND UPS is illuminated, it indicates a UPS fault. First, remove all loads from the UPS outlets. Then, turn off the UPS and disconnect it from the mains. Reconnect the UPS to the mains and turn it back on. If the problem continues, contact LEGRAND Technical Support.
  • A
    anthony14Aug 23, 2025
    Why does my LEGRAND KEOR SP 1000 make intermittent alarm sounds in normal mode?
    • A
      Anthony OsbornAug 23, 2025
      The intermittent alarm sound on your LEGRAND UPS during normal mode indicates an overload. To resolve this, disconnect some non-critical loads from the UPS outlets until the overload condition is resolved.
  • C
    Crystal WoodsAug 28, 2025
    What to do if my LEGRAND KEOR SP 1000 UPS has a strange noise or smell?
    • D
      daniellebentonAug 28, 2025
      If your LEGRAND UPS emits a strange noise or smell, it indicates a fault. Immediately shut down the UPS and unplug it from the mains socket. Contact LEGRAND Technical Support.
  • S
    Sergio KellySep 3, 2025
    How to fix LEGRAND KEOR SP 1000 when backup time is short?
    • T
      Taylor HullSep 3, 2025
      If the backup time of your LEGRAND UPS is shorter than expected, it could be due to a low battery or a battery fault. If the backup time remains unsatisfactory after 8 hours of battery charging, contact LEGRAND Technical Support.

LEGRAND KEOR SP 1000 Specifications

General IconGeneral
Power Rating1000 VA
Output Power600 W
Input Voltage230 V
Output Voltage230 V
Number of Outlets4
TechnologyLine-Interactive
Communication PortUSB
Frequency50/60 Hz
WaveformSimulated Sine Wave
Communication InterfaceUSB
Battery TypeLead Acid
Typical Recharge Time4-6 hours
OutletsIEC C13