condition of compressor activation/halt:
The shortest operation time and halt time of compressor should be met.
6.7 Fault detection and protection
Compressor protection
the shortest halt time of compressor is 3 min. and it must be re-initiated for
fault detection and actions after at least 3 min.
!
The fault codes appears in case of malfunction alarms
Fault
enclosure temperature
capillary fault
Overtemperature
alarm
Code
Delay
0 s 2 s
Duration
Reset
Remarks
alarm
compressor halt
alarm
auto
0 s 2 s
auto
The compressor will restart in 1 min. delay after the reset of compressor and the
downtime of compressor is larger than the shortest halt time(3 min.)
Fault codes lookup
in case of new fault, the Nixie tubes get to show the relative information;press
“▲+SET in the main interface to look up the first malfunciton in record when
the reset is not proceeded, press“ or to repeatedly find the other
faults in queue, press“▲+SETto quite the fault lookup interface.
!
HTTP://WWW.LEI ZIG.COM 26
condition of its stoppageinside temperature<[ fan starting 15]-2 celsius(defult 12 celsius).
logic control of external circuit fan
external fan and compressor delay to coordinate, after 5 s of compressor activation,eternal
fan is started; while the fan is halted after 5 s of compressor stoppage.
compressor of external circuit fan
after 10 s of internal fan activation, system checks if the inside temperature can be met to
start up the compressor
condition of its activationinside temperatre≥[ refrigerating temperature](defalut 35
celsius,settable);
cndition of its haltinside temperature <[refrigerating temperature]- [difference
3](default 32 celsius).