EasyManua.ls Logo

Leizig FCC225 - Application; Technical Data and Cutout Drawing

Leizig FCC225
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HTTP://WWW.LEIZIG.COM
11
FCC225/320/225Q/320Qdimension drawing:
2Technical data and cutout drawing
FCC225P/320P dimension drawing & cutout drawing
1 5 5
300
560
526
155
55
18
300
264
450
56
530
560
14
4
- 9
260
300
560
30
300
53
194
32
560
170
161148
230
35
490
4
- 9
Enclosure cooling unit is specifically designed to cool the outdoor cabinet. It protects the inside costly
components sensitive to temperature by dispersing heat load out of the cabinet and is particularly suitable
for the condition under the temperature range from 35to 55℃, with the effect surpassing other heat
dissipation items such as air/air heat exchanger and filter fan unit.
230
278
1Application
264
530
FCC225Q/320Qcutout drawing:
FCC225/320cutout drawing:
FCC225 FCC225P FCC225Q
30200001 30200049 30200547
FCC320 FCC320P FCC320Q
30200002 30200050 30200548
19 20 19
18 19 18
ID#
Model#
col.
FCC225 FCC320
225
180
R134a/60g
20-55
230
202
50Hz
220-240
253
300x560x155
320
260
R134a/70g
20-55
230
258
50Hz
220-240
322
300x560x155
IP54
55dB(A)
IP54
55dB(A)
cooling output W(L35L35)
cooling output W(L35L50)
refrigerant
Ambient temperature
o
C
rated voltageV
rated frequencyHz
Range of operationV
DimensionWxHxDmm
weight Kg
Protection category
Noise level
Fitting
power consumption W(L35L35)
power consumption W(L35L50)
semi-recessed external boltless semi-recessed external boltless