IOM / ROOFTOP BALTIC Series - 0704-E Page 109
control interfaces ds50 menu tree
Main Screen Code Description Code Description Code Description Code UNIT Min Factory Max Description
9-Com. 3900 1-Display 3910 Sp Mini. 3911 °c 8 17 21 [ Mode] Minimum temperature for the required
room temperature set point at the middle
of the dead zone.
Sp Maxi. 3912 °c 21 27 35 [ Mode] Maximum temperature for the required
room temperature set point at the middle
of the dead zone.
Offset 3913 °c -5 0 5 Offset of the value measured by the ambient
temperature sensor
Standard Sp 3914 Yes/No ~ No ~ Allows a reset of ALL set point to standard factory
settings (when available).No possible for
configurations. And clock as there is no factor
settings for these.
2-Link 3920 ID 3921 ~ 1 1 12 [ Configuration ] Identification address for the unit
from 1 to 12.
Number 3922 ~ 1 1 12 [ Configuration ] Number of units on the BUS.
Unit with address N°1 is always the master.
Type. 3923 List 0 0 6 Master / Slave relationship: refer to
"Control Communication Links" p?
Type 3924 List 0 0 2 Configuration of the sharing of the Outdoor
humidity and temperature.
3-BMS 3930 ID 3931 ~ 1 1 200 [ Configuration ] Identification number
on the 485 Bus
Type 3932 List 0 2 Climatic, ModBus or LonWorks
Baud 3933 List 3 4 1200, 2400, 4800, 9600 or 19200
Watchdog 3934 ~ 0 0 1000 [ BMS ] Activation of the control by a computer or
an automat - mode BMS is activated if this value
is different from zero, This value is decreased
every second
BMS Unoc. 3935 On/Off ~ Off ~ [BMS] Cancel the override unoccupied mode
Speed 3936 On/Off ~ Off ~ Blower Speed Control in the dead zone:
[ON] the unit runs in Low Speed mode
[OFF] the unit runs in High Speed mode