Page 104 - IOM / ROOFTOP BALTIC Series - 0704 - E
control interfaces ds50 menu tree
Main Screen Code Description Code Description Code Description Code UNIT Min Factory Max Description
6-Capacity 3360 Room 3361 ~ 1 4 50 [Capacity Factor] Reactivity : Refer to
"Control Software Features" p ?
Reheat 3362 ~ 1 4 50 [Capacity Factor] Reactivity: Refer to
"Control Software Features" p ?
Dehu. 3363 ~ 1 4 50 [Capacity Factor] Reactivity:
Refer to "Control Software Features" p ?
Humi. 3364 ~ 1 4 50 [Capacity Factor] Reactivity:
Refer to "Control Software Features" p ?
7-Safety 3370 Room Low 3371 °c 5 5 20 [Safety Limit] Room temperature "Low Limit" in °C
Threshold of activation of an alarm
Room High 3372 °c 20 40 40 [Safety Limit] Room temperature
"High Limit" in °C Threshold of activation
of an alarm
Sup.Lo.1 3373 °c
9or5 10or8 19
[Safety Limit] Supply temperature low Limit(in °c)
- Threshold of activation of the 1° level of security:
Reduce the Capacity Factor by one stage of
compressor and switch to minimum Fresh Air.
Sup.Lo.2 3374 °c
7 or 3 8 or 6 17
[Safety Limit] Supply temperature low Limit (in °c)
- Threshold of activation of the 2° level of security:
Reduce the Capacity Factor to zero and switch to
0% Fresh Air, open the HWC valve.
Sup.Lo.3 3375 °c
5 or 1 6 or 2 15
[Safety Limit] Supply temperature low Limit (in °c)
- Threshold of activation of the 3° level of security.
- Alarm threshold, the unit is switched off.
Sup.Hi.1 3376 °c 20 40 70 [Safety Limit] Supply temperature high Limit (in °c)
Threshold of activation of the 1° level of security:
reduce the capacity factor by one stage of
compressor. Close the HWC valve.
Sup.Hi.2 3377 °c 20 60 70 [Safety Limit] Supply temperature high Limit (in °c)
- Threshold of activation of the 2° level of security:
Alarm threshold: Reduce the capacity factor to 0
Room Low 3378 % 0 0 1000 [Safety Limit] Room relative humidity low Limit
(in %) - Threshold of activation of the alarm
Room High 3379 % 0 1000 1000 [Safety Limit] Room humidity high Limit (in %)
- Threshold of activation of the alarm
4-Ventilation 3400 3410 Air Flow 3411 pa 0 25 1000 [Safety Limit] Airflow Detection Threshold of
pressure difference in Pa indicating Low Airflow
Rate. If the pressure difference across the filter is
lower than this threshold the safety is activated.
. No Filter 3412 pa 0 50 1000 [Safety Limit] Missing Filters. Threshold of
pressure difference in Pa indicating absence of
filters. If the pressure difference across the filter is
lower than this threshold the safety is activated.
. Dirty Fil. 3413 pa 0 250 1000 [Safety Limit] Dirty Filters. Threshold of pressure
difference in Pa indicating Filters are Dirty. If the
pressure difference across the filter is Higher
than this threshold the safety is activated.