Page 112 - IOM / ROOFTOP BALTIC Series - 0704 - E
ELECTRICAL DATA - CONTROL variables
MODBUS
Settings and Readings
@ (hexa) @ (deci) DC50
11H 17 R/W L [Dry contact] Digital Output, Free 1, BM50-J17-NO12 2141
12H 18 R/W L [Dry contact] Digital Output, Free 2, BE50-J5-NO1 2142
13H 19 R/W L [Dry contact] Digital Output, Free 3, BE50-J6-NO2 2143
14H 20 R/W L [Dry contact] Digital Output, Free 4, BE50-J7-NO3 2144
15H 21 R/W L [Dry contact] Digital Output, Free 5, BE50-J8-NO4 2145
16H 22 R/W L not used
17H 23 R/W L not used
18H 24 R/W L not used
19H 25 R/W L not used
1AH 26 R/W L not used
1BH 27 R/W L not used
1CH 28 R/W L not used
1DH 29 R/W L not used
1EH 30 R/W L not used
1FH 31 R/W L not used
20H 32 R/W L not used
21H 33 R L [Alarm] General 1000
22H 34 R L [On/Off] Fan, Blower 2315
23H 35 R L [On/Off] Fan, Extraction 2321
24H 36 R L [On/Off] Compressor, 1 2516
25H 37 R L [On/Off] Compressor, Heat pump, 1 2517
26H 38 R L [On/Off] Compressor, 2 2526
27H 39 R L [On/Off] Compressor, Heat pump, 2 2527
28H 40 R L [On/Off] Compressor, 3 2536
29H 41 R L [On/Off] Compressor, Heat pump, 3 2537
2AH 42 R L [On/Off] Compressor, 4 2546
2BH 43 R L [On/Off] Compressor, Heat pump, 4 2547
2CH 44 R L [On/Off] Gas, Burner, 1 2615
2DH 45 R L [On/Off] Gas, Burner, 2 2616
2EH 46 R L [On/Off] Gas, Burner, High power, 1 2617
2FH 47 R L [On/Off] Electrical heaters, 1 2625
30H 48 R L [On/Off] Electrical heaters, 2 2626
31H 49 R L [Dry contact] Digital Input, Free 1, BM50-J8-ID13 2151
32H 50 R L [Dry contact] Digital Input, Free 2, BM50-J8-ID14 2152
33H 51 R L [Dry contact] Digital Input, Free 3, BE50-J4-ID1 2153
34H 52 R L [Dry contact] Digital Input, Free 4, BE50-J4-ID2 2154
35H 53 R L [Dry contact] Digital Input, Free 5, BE50-J4-ID3 2155
36H 54 R L [Dry contact] Digital Input, Free 6, BE50-J4-ID4 2156
37H 55 R L not used
38H 56 R L not used
39H 57 R L not used
3AH 58 R L not used
3BH 59 R L not used
3CH 60 R L not used
3DH 61 R L not used
3EH 62 R L not used
3FH 63 R L not used
40H 64 R L not used