Page 114 - IOM / ROOFTOP BALTIC Series - 0704 - E
ELECTRICAL DATA - CONTROL variables
MODBUS
Settings and Readings
@ (hexa) @ (deci) DS50
20H 32 R/W not used
21H 33 R 1 = 1 [Alarm] Code Error 1000
22H 34 R 10 = 1.0°c [Temperature] Room 2112
23H 35 R 10 = 1.0°c [Temperature] Outdoor 2111
24H 36 R 10 = 1.0°c [Temperature] Supply 2113
25H 37 R 10 = 1.0°c [Temperature] Return 2114
26H 38 R 10 = 1.0% [Relative Humidity] Room 2122
27H 39 R 10 = 1.0 g/Kg [Absolute Humidity] Room 2124
28H 40 R 10 = 1.0% [Relative Humidity] Outdoor 2121
29H 41 R 10 = 1.0 g/Kg [Absolute Humidity] Outdoor 2123
2AH 42 R 1 = 1 pa [Flow] Differential pressure on the air, in pascal 2131
2BH 43 R 1 = 1 ppm [CO²] Level in ppm 2132
2CH 44 R 1 = 1% [% of opening] Register of fresh air 2413
2DH 45 R 1 = 1% [% of opening] Valve gas 2618
2EH 46 R 1 = 1% [% of opening] Electrical heaters (Triac) 2627
2FH 47 R 1 = 1% [% of opening] Hot water coil 2633
30H 48 R 1 = 1% [% of opening] Humidifier 2714
31H 49 R 10 = 1.0°c [Dry contact] Temperature, Free 1, BE50-J9-B1 2161
32H 50 R 10 = 1.0°c [Dry contact] Temperature, Free 2, BE50-J9-B2 2162
33H 51 R 10 = 1.0°c [Dry contact] Temperature, Free 3, BE50-J10-B3 2163
34H 52 R 10 = 1.0°c [Dry contact] Temperature, Free 4, BE50-J10-B4 2164
35H 53 R 10 = 1.0% [Dry contact] Humidity, Free 1, BE50-J9-B1 2165
36H 54 R 10 = 1.0% [Dry contact] Humidity, Free 2, BE50-J9-B2 2166
37H 55 R 10 = 1.0% [Dry contact] Humidity, Free 3, BE50-J10-B3 2167
38H 56 R 10 = 1.0% [Dry contact] Humidity, Free 4, BE50-J10-B4 2168
39H 57 R not used
3AH 58 R not used
3BH 59 R not used
3CH 60 R not used
3DH 61 R not used
3EH 62 R not used
3FH 63 R not used
40H 64 R not used