IOM / ROOFTOP BALTIC Series - 0704-E Page 61
VENTILaTION : AIRFLOW BALANCING
070
030-035
At10-8G2L
(*)
EXHAUST ROOFCURB
(*) The performances of twin fan units can be calculated starting from the corresponding operation point for a single fan
(see the figure behind) by applying the formulas below.
- pressure : PTwin = P x 1
- volume flow rate : Qb = Q x 2
- impeller power: Wb = W x 2,15
- fan speed : Nb = N x 1,05
- Lws : Lwsb = Lws + 3 dB