• 38 • Installation Manual • COMPACTAIR ADV IOM-MIL157E-0418
3.- COMMISSIONING AND OPERATION
3.3.- CLIMATIC™ CONFIGURATION
Settings
1. Supply Air-fl ow adjustement (depending on customer requirements)
a. 3333 = nominal air fl ow / pressure
b. 3334 = reduced air fl ow / pressure
2. Scheduling (depending on customer requirements)
a. Zones & Modes (Night/Day/Day I/ DayII)
b. Setpoints per mode
3. Regulation temperature probe selection
a. Select the regulation probe (DC, Return, Customer, etc.) in the Room Temp. Confi g screen
4. Outside temperature probe selection
a. Select the outdoor temp probe (Unit, Customer) in the Outside Temp. Confi g screen
5. Air quality sensor selection (optional)
a. Select the air quality CO2 sensor (Remote, Customer) in the CO2 Confi g screen
6. Remote display confi guration
a. 3151 = DC simple / DC full / DM
7.Minimum fresh air
a. 3121 = minimum opening %