20
1.- GENERAL CHARACTERISTICS
0
(*) Add to the unit data.
MODELS (OUTDOOR UNIT)
DIMENSIONS
A
B
22E-24E-28E-32E
122,5
38E
122,5
44D-48D-56D-64D
44D2-48D2-56D2-64D2
150,5
76D/D2
150,5
WEIGHTS kg (*)
15
20
30
40
102,5
102,5
150,5
150,5
970
1095
1949
2199
C
165
165
165
165
D
342
407
342
407
E
996,5
996,5
996,5
996,5
F
(*) Add to the unit's weight.
MODELS LEC / H (INDOOR)
(A)
230 / III
400/ III
POWER (*) kW
22E
0,2
0,5
0,3
24E
0,4
1,0
0,6
28E
0,8
2,0
1,2
32E
1,0
2,5
1,4
38E
1
2,5
1,4
44D
0,4
1,0
0,6
48D
0,8
2,0
1,2
56D
1,5
3,8
2,2
64D
1,5
3,8
2,2
76D
1,7
4,3
2,5
MODELS KVC / H (OUTDOOR)
(A)
230 / III
400/ III
POWER (*) kW
WEIGHTS Kg (*)
22E
0,4
1,0
0,6
15
24E
0,6
1,5
0,9
15
28E
0,8
2,0
1,2
15
32E
__
__
__
__
38E
__
__
__
__
44D/D2
0,8
2,0
1,2
30
48D/D2
1,2
3,0
1,7
30
56D/D2
1,6
4,0
2,3
30
64D/D2
__
__
__
__
76D/D2
__
__
__
__
02 2055999
WEIGHTS Kg (*)
MAXIMUM
CURRENT (*)
MAXIMUM
CURRENT (*)
It is based on one or two dampers located on the outdoor
unit discharge air, which lets you control condensation
temperature through the air flow.
The damper is moving by a servomotor, which receives a
proportional signal through a pressure detector.
PROPORTIONAL CONDENSING PRESSURE CONTROL BY DAMPERS
KIT MORE STATIC PRESSURE OF AIR DISCHARGE
It is an specific fan to obtain more available static pressure up to 350Pa for outdoor unit and 400Pa for indoor unit.
See air flow data section for optional fan performances.
Electrical data for these optional fans:
Thus the unit will be able to operate in the cooling cycles
when the outdoor temperature is until -10ºC.
COMPRESSOR STARTING CURRENT CONSTRAINED (SOFT STARTER) 400V-III
It is an electronic element, which reduces the
peak compressor starting current up to 40%
(see pages of electrical data without soft starter)
Only available for 400V-III units.
This kit is not available with kit vertical discharge
outdoor unit at the same time.
D
A
C
B
E
F
DAMPER
DAMPER
ACTUATOR
1.6.- AVAILABLE OPTIONS
Dimensions of dampers for this kit:
MODELS (OUTDOOR UNIT)
22E-24E-28E-32E-38E
44D/D2-48D/D2-56D/D2-64D/D2-76D/D2
WEIGHTS (*)
3
6
(*) Add to the unit's weight.