EasyManua.ls Logo

Lennox EL195UHE - INSTALLATION: PIPE AND FITTING SPECIFICATIONS; PIPE, FITTINGS, PRIMER, AND CEMENT REQUIREMENTS

Lennox EL195UHE
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 19
TABLE 5
Maximum Allowable Vent Length in Feet
NOTE - Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total. Both Intake
and Exhaust must be same pipe size.
NOTE - Additional vent pipe and elbows used to terminate the vent pipe outside the structure must be included in the total vent
length calculation.
Standard Termination at Elevation 0 - 4500 ft
Number
Of 90°
Elbows
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
030
045
070 090 110 135
030,
045
070 090 110 135
030,
045
070 090 110 135
1 81 66 44 24
n/a
115 115 93 58
n/a
138 137 118 118 114
2 76 61 39 19 110 110 88 53 133 132 113 113 109
3 71 56 34 14 105 105 83 48 128 127 108 108 104
4 66 51 29
n/a
100 100 78 43 123 122 103 103 99
5 61 46 24 95 95 73 38 118 117 98 98 94
6 56 41 19 90 90 68 33 113 112 93 93 89
7 51 36 14 85 85 63 28 108 107 88 88 84
8 46 31
n/a
80 80 58 23 103 102 83 83 79
9 41 26 75 75 53 18 98 97 78 78 74
10 36 21 70 70 48 13 93 92 73 73 69
Standard Termination Elevation 4500 - 10,000 ft
Number
Of 90°
Elbows
2” Pipe 2-1/2” Pipe 3” Pipe
Model Model Model
030,
045
070 090 110 135
030,
045
070 090 110 135
030,
045
070 090 110 135
1 81 66 44
n/a n/a
115 115 93 58
n/a
138 137 118 118 114
2 76 61 39 110 110 88 53 133 132 113 113 109
3 71 56 34 105 105 83 48 128 127 108 108 104
4 66 51 29 100 100 78 43 123 122 103 103 99
5 61 46 24 95 95 73 38 118 117 98 98 94
6 56 41 19 90 90 68 33 113 112 93 93 89
7 51 36 14 85 85 63 28 108 107 88 88 84
8 46 31
n/a
80 80 58 23 103 102 83 83 79
9 41 26 75 75 53 18 98 97 78 78 74
10 36 21 70 70 48 13 93 92 73 73 69

Other manuals for Lennox EL195UHE

Related product manuals