Page 46
Gas Pressure Adjustment
Gas Flow (Approximate)
TABLE 13 
GAS METER CLOCKING CHART
EL195UHE 
Unit
Seconds For One Revolution
Natuarl LP/Propane
1 cu ft 
Dial
2 cu ft 
Dial
1 cu ft 
Dial
2 cu ft 
Dial
-030 120 240 300 600
-045 80 160 200 400
-070 55 110 136 272
-090 41 82 102 204
-110 33 66 82 164
-135 27 54 68 136
                       Natural-1000 btu/cu ft  LP-2500 btu/cu ft
Furnace should operate at least 5 minutes before check-
ing gas  ow. Determine  time in  seconds  for two revolu-
tions of gas through the meter. (Two revolutions assures a 
more accurate time.) Divide by two and compare to time 
in table 13 below. If manifold pressure matches table 14 
and rate is incorrect, check gas orices for proper size and 
restriction. Remove temporary gas meter if installed.
NOTE - To obtain accurate reading, shut off all other gas 
appliances connected to meter.
Supply Pressure Measurement
When testing supply gas pressure, use the 1/8” N.P.T. 
plugged tap or pressure post located on the gas valve 
to facilitate test gauge connection. See gure 60. Check 
gas  line  pressure  with  unit  ring  at  maximum  rate.  Low 
pressure may result in erratic operation or underre. High 
pressure can result in permanent damage to gas valve or 
overre.
On multiple unit installations, each unit should be checked 
separately, with and without units operating. Supply pres-
sure must fall within range listed in table 14.
Check Manifold Pressure
After supply pressure has been checked and adjusted, 
check manifold pressure. Move pressure gauge to outlet 
pressure tap located on unit gas valve (GV1). Checks of 
manifold pressure are made as verication of proper reg-
ulator adjustment.
 IMPORTANT
For safety, connect a shut-off valve between the 
manometer and the gas tap to permit shut off of gas 
pressure to the manometer.
1 -   Connect the test gauge positive side “+“ to manifold 
pressure tap on gas valve.
2 -  Tee into the gas valve regulator vent hose and 
connect to test gauge negative “-”.
3 -  Start unit and let run for 5 minutes to allow for steady 
state conditions.
4 -  After allowing unit to stabilize  for 5 minutes, record 
manifold pressure and compare to value given in 
table 14.
5 -  Shut unit off and remove manometer as soon as an 
accurate reading has been obtained. Take care to 
replace pressure tap plug.
6 -  Start unit and perform leak check. Seal leaks if found.
TABLE 14 
Supply Line and Manifold Pressure (inches w.c.)
Unit Fuel
Manifold 
Pressure
Line Pressure
All Nat 3.5 4.5 - 10.5
All LP/Propane 10.0
11.0 - 13.0
Proper Combustion
Furnace should operate minimum 15 minutes with correct 
manifold pressure and gas ow rate before checking com-
bustion. Take  combustion  sample beyond the  ue  outlet 
and compare to the tables below. The maximum carbon 
monoxide reading should not exceed 100 ppm.
TABLE 15 
EL195UHE Unit CO2% Nat CO2% LP
-030
7.2 - 7.8 7.5 - 9.0
-045
-070
-090
-110
-135
High Altitude Information
NOTE - In Canada, certication for installations at eleva-
tions  over  4500  feet  (1372 m) is the  jurisdiction  of  local 
authorities.
Units may be installed at altitudes up to 10,000 ft. above 
sea level. See table 17 for de-rate manifold values. Units 
installed at altitude of 7501 - 10,000 feet require an orice 
change. Units installed at altitude of 4501 - 10,000 feet 
require a pressure switch change which can be ordered 
separately. Table 17 lists conversion kit and pressure 
switch requirements at varying altitudes.
The combustion air pressure switch is factory-set and re-
quires no adjustment.