Lennox EL195UHE - IV-HEATING SYSTEM SERVICE CHECKS; GAS PIPING INSTALLATION, TESTING, AND PRESSURE MEASUREMENT

Lennox EL195UHE
55 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Page 43
TABLE 11
-02 IGNTION CONTROL
RED LED
Flash Code
Diagnostic Codes / Status of Furnace
Off No power to control or board fault detected
Heartbeat
1
Control powered - displayed during all modes of operation if no errors are detected
1 Reverse Line Voltage Polarity
2 Improper Earth Ground
3 Burner failed to light, or lost ame during heat demand
4 Low Flame Signal - check ame sensor
5
Watchguard - burner failed to light, exceeded maximum number of retries or
recycles.
6 Not Used
7
Primary or Secondary Limit Open or Watchguard Mode - Limit Switch Open longer
than 3 minutes
8 Rollout Switch Open
9 Pressure Switch failed to close or opened during heat demand
10 Watchguard - Pressure Switch opened 5 times during one heat demand
11 Pressure Switch stuck closed prior to activation of combustion air inducer
12 Flame Sensed without gas valve energized
13 Low Line Voltage
Note - 1 Notes
Note A ”Heartbeat” is indicated by a ”Slow Flash” - 1 sec on 1 sec off, repeating
Note
Last 10 error codes are stored in memory including when power is shut off to the
unit. - To recall, pressand release button, most recent will be displayed rst, LED off for 3
sec, then next error code is displayed, etc. To clear error codes, depress and hold button
longer than 5 seconds.