Page 21
7. Combustion Air Inducer (B6) and Cold End Header 
Box
All units use a two-speed combustion air inducer to move 
air through the burners and heat exchanger during heating 
operation. The blower uses a 120VAC motor. The motor 
operates during all heating operation and is controlled by 
integrated control control A92. The inducer also operates 
for 15 seconds before burner ignition (pre-purge) and for 5 
seconds after the gas valve closes (post-purge).
The  inducer  operates  on  low  speed  during  rst-stage 
heat, then switches to high speed for second stage heat. 
The  combustion  air  inducer  is  installed  on  the  cold  end 
header  box  (CEHB). The  cold  end  header  box  is  a  sin-
gle piece  made of hard  plastic. The box has an  internal 
channel  where  the  combustion  air  inducer  creates  neg-
ative  pressure  at unit  start up. The  channel contains  an 
orice used to regulate ow created by the combustion air 
inducer. The box has pressure taps for the combustion air 
inducer pressure switch hoses. The pressure switch mea-
sures the pressure dierential across the cold end head-
er  box  orice  or  dierence  in  the  channel  and  the  box. 
If replacement is necessary the gaskets used to seal 
the box to the vestibule panel and the combustion air 
inducer to the box, must also be replaced.
A  pressure  switch  measures  the  pressure  dierential 
across the CEHB orice to prove inducer operation. The 
CEHB  orice  will  be  dierent for  each model.  See table 
10 for orice  sizes.  When  the proving switch opens, the 
furnace control (A92) immediately closes the gas valve to 
prevent burner operation.
TABLE 10 
Unit CEHB Orice Size
-045 0.618
070-1, -2 0.810
-070-3 and later 0.920
-090 0.920
-110 1.040
8. Combustion Air Inducer Pressure Switch (S18) 
(Figure 16)
Units  are equipped  with a  dual  combustion  air  pressure 
switch (rst and second stage) located on the CEHB. The 
switch is connected to the cold end header box by means 
of exible silicone hoses. It monitors negative dierential 
pressure across the cold end header box orice.
The  switches  are  a  single-pole  single-throw  pressure 
switches electrically  connected to the integrated  control. 
The purpose of the switches is to prevent burner operation 
if the combustion air inducer is not operating, the inlet or 
exhaust  pipes  or  heat  exchanger  are  restricted.On  heat 
demand (rst or second stage) the switch senses that the 
combustion air inducer is operating. It closes a circuit to 
the integrated control when pressure across the CEHB or-
ice becomes greater then the switch set point
Set points vary depending on unit size. See table 11. Both 
pressures  sensed  by  the  switches  are  negative  relative 
to atmospheric pressure. If the inlet or exhaust pipes, or 
the heat exchanger become obstructed, the switch sens-
es the loss of dierential pressure and opens the circuit to 
the furnace integrated control and gas valve. A bleed port 
on the  switch allows  relatively dry  air  in the  vestibule to 
purge switch tubing, to prevent condensate build up.
3/16 Terminals
Low Fire Switch
High Fire Switch
1/4
" Terminals
Tap (negative - )
Tap (positive +)
Combustion Air Inducer Pressure Switch
FIGURE 16 
NOTE - The switch is factory set and is not eld adjust-
able. It is a safety shut-down control in the furnace and 
must not be by-passed for any reason. If switch is closed 
or bypassed, the control will not initiate ignition at start up.
TABLE 11 
0- 4500’
Unit Set Point Low Heat Set Point High Heat
-045 0.35 0.60
-070-1, -2 0.45 0.90
-070-3 & later 0.45 0.81
-090 0.50 0.90
-110 0.45 0.90
TABLE 12 
4501 - 7500’
Unit Set Point Low Heat Set Point High Heat
-045 0.35 0.55
-070-1, -2 0.45 0.81
-070-3 & later 0.45 0.70
-090 0.50 0.85
-110 0.45 0.81
TABLE 13 
7501 - 10,000’
Unit Set Point Low Heat Set Point High Heat
-045 0.35 0.50
-070-1, -2 0.41 0.74
-070-3 & later 0.40 0.65
-090 0.45 0.81
-110 0.41 0.74