Page 6
I-UNIT COMPONENTS
EL296DFE  unit  components are  shown  in  gure  1. The 
gas valve, combustion air inducer and burners can be ac-
cessed by removing the access panel. Electrical compo-
nents are in the control box (gure 2) found in the blower 
section.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
 CAUTION
Electrostatic  discharge  can  aect 
electronic components. Take precautions 
to neutralize electrostatic charge by 
touching your hand and tools to metal 
prior to handling the control.
A- Control Box
1. Control Transformer (T1)
A  transformer located  in the  control box  provides  power 
to the low voltage section of the unit. Transformers on all 
models  are  rated  40VA  with  a  120V  primary  and  a  24V 
secondary.
2. Door Interlock Switch (S51)
A door interlock switch is wired in series with line voltage. 
When the inner blower access panel is removed the unit 
will shut down.
Transformer
Circuit Breaker
SureLight
®
Integrated
Control
Interlock Switch
FIGURE 2 
3. Circuit Breaker (CB8)
A 24V circuit breaker is also located in the control box. The 
switch provides overcurrent protection to the transformer 
(T1). The breaker can be manually reset by pressing the 
button on the face. See gure 3.
CIRCUIT BREAKER CB8
PRESS TO RESET
FIGURE 3 
 WARNING
Shock hazard.
Disconnect power before servicing. Integrated 
control is not eld repairable. If control is inoperable, 
simply replace entire control.
Can cause injury or death. Unsafe operation will 
result if repair is attempted.
4. Integrated Control (A92)
Units  are  equipped  with  the  SureLight
®
  two-stage,  inte-
grated control. The system consists of a ignition / blower 
control (gures 4 and 5) with control pin designations in ta-
bles 1 and 2 and ignitor (gure 14). The control and ignitor 
work in combination to ensure furnace ignition and ignitor 
durability. The control provides gas ignition, safety checks 
and indoor blower control with two-stage gas heating.
The furnace combustion air inducer, gas valve and indoor 
blower are controlled in response to various system inputs 
such as thermostat signal, pressure and limit switch signal 
and ame signal. The control features  a  seven-segment 
LED  display,  indicating  furnace  status  and  error  codes. 
The  LED  ashes  in  single  digits.  For  example  using  ta-
ble 4 under LIMIT CODE, an “E” followed by “2” followed 
by “5” followed by “0”, the limit switch circuit is open. The 
control also has two unpowered (dry) 1/4” contacts for a 
humidier and a 120 volt accessory terminal. Both rated 
at (1) one amp each. 
Electronic Ignition
At  the  beginning  of  the  heat  cycle  the  integrated  con-
trol  monitors  the  rst  stage  and  second  stage  combus-
tion air  inducer pressure switch. The  control will not  be-
gin the heating cycle if the rst stage pressure switch is 
closed(bypassed). Likewise the integrated control will not 
begin the second stage heating cycle if the second stage 
pressure  switch  is  closed,  and  will  remain  in  rst  stage 
heat. However, if the second stage pressure switch closes 
during the rst stage heat pre-purge, the control will allow 
second stage heat. Once the rst stage pressure switch 
is  determined  to  be open,  the combustion  air  inducer  is 
energized on low (rst stage) heat speed. When the dier-
ential in the pressure switch is great enough, the pressure 
switch closes and a 15-second pre-purge begins