Height
H
(feet)
10
15
20
30
TABLE 5
CAPACITY OF TYPE B DOUBLE-WALL VENTS WITH SINGLE-WALL METAL CONNECTORS
Lateral
L
(feet)
0
2
4
6
0
2
5
8
0
2
5
10
0
2
5
10
15
O
2
5
10
15
20
0
2
5
lO
15
20
30
MIN
38
39
NR
NR
37
39
NR
NR
37
39
52
NR
36
38
51
NR
NR
35
37
5O
NR
NR
NR
34
37
49
NR
NR
NR
NR
SERVING A SINGLE CATEGORY I APPLIANCE
Vent and Connector Diameter - D (inches)
3 Inch 4 Inch 5 Inch
Appliance Input Rating in Thousands of Btu Per Hour
MAX
77
51
NR
NR
83
56
NR
NR
87
61
56
NR
93
69
63
NR
NR
96
74
68
NR
NR
NR
99
80
74
NR
NR
NR
NR
MIN
59
6O
74
83
58
59
77
90
57
59
76
97
56
57
75
95
NR
54
56
73
93
NR
NR
53
55
72
91
115
NR
NR
MAX
151
96
92
89
164
108
102
95
174
117
111
100
190
136
128
116
NR
200
148
140
129
NR
NR
21t
164
157
144
131
NR
NR
MIN
85
85
102
114
83
83
107
122
82
82
105
132
80
8O
102
128
158
78
78
100
125
155
186
76
76
98
122
151
181
NR
MAX
249
156
152
147
273
176
168
161
293
193
185
171
325
225
216
201
186
346
248
239
223
208
192
372
281
271
255
239
223
NR
6 Inch
MIN
126
123
146
163
123
121
151
175
120
119
148
188
116
115
t44
182
220
114
113
141
177
216
254
110
109
136
171
208
246
NR
MAX
373
231
225
220
412
261
252
243
444
287
277
261
499
337
326
3O8
29O
537
375
363
344
325
306
584
429
417
397
377
357
NR
NOTE: Singleapp4ianoaver_ngconfigurationswithzero laterallengthsare assumedto have noelbowsin theventsystem.Forallothervent_figura_ons, the vent
a o
system isassumedtohavetwo90 eibow,_Fo_each ad_N_al _0° elboworequtva_t (f_ exampleIwo45 etoowsequalonegO=elbowJbeyondtwo.themaximum
capacitylistedin the ventingtable shouldbe reducedby 10 percent(0.90 x maximumlistedcapaclty_.
Page 16