EasyManuals Logo

Lennox G27M Series Unit Information

Lennox G27M Series
28 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background image
Page 12
IV–HEATING SYSTEM SERVICE CHECKS
AA.G.A. / C.G.A. Certification
All G27M units are A.G.A. / C.G.A. design certified with-
out modifications. Refer to the G27M Installation
Instruction for Information.
B–Gas Piping
Gas supply piping should not allow more than 0.5”W.C.
drop in pressure from unit with gas valve off and with
unit operating at second–stage heat (high fire). Supply
gas pipe must not be smaller than unit gas connection.
Refer to table 6 if pressure drop exceeds 0.5”W.C. or if
gas piping is suspect. Do not operate furnace below
nameplate minimum line pressure.
C–Testing Gas Piping
IMPORTANT
In case emergency shutdown is required, turn off
the main shut-off valve and disconnect the main
power to unit. These controls should be properly
labeled by the installer.
When pressure testing gas lines, the gas valve must be
disconnected and isolated. Gas valves can be damaged
if subjected to more than 0.5psig (14” W.C.). See figure
16
.
If the pressure is equal to or less than 0.5psig
(14”W.C.), use the manual shut–off valve before
pressure testing to isolate furnace from gas supply.
FIGURE 16
MANUAL MAIN SHUT–OFF VALVE
GAS VALVE WILL NOT HOLD TEST
PRESSURE IN EXCESS OF 0.5
PSIG (14”W.C.)
GAS VALVE
CAP
GAS PIPING TEST PROCEDURE
FIELD PROVIDED
LINE PRESSURE TAP
When checking piping connections for gas leaks, use
preferred means. Kitchen detergents can cause harmful
corrosion on various metals used in gas piping. Use of a
specialty gas leak detector is strongly recommended. It
is available through Lennox under part number
31B2001. See Corp. 8411–L10, for further details.
Do not use matches, candles, flame or any other source
of ignition to check for gas leaks.
D–Testing Gas Supply Pressure
When testing supply gas pressure, connect test gauge to
inlet pressure tap (field provided). See figure 16. Check
gas line pressure with unit firing at maximum rate. Low
pressure may result in erratic operation or underfire. High
pressure can result in permanent damage to gas valve or
overfire. For natural gas units, operating pressure at unit
gas connection must be a minimum of 5.0” W.C. but no
more than 13.0”W.C. at any time.
TABLE 6
GAS PIPE CAPACITY – FT
3
/HR (kL/HR)
Nominal
IPiSi
Internal
Di
Length of Pipe–Feet(m)
Iron Pipe Size
–Inches(mm)
Diameter
–Inches(mm)
10
(3.048)
20
(6.096)
30
(9.144)
40
(12.192)
50
(15.240)
60
(18.288)
70
(21.336)
80
(24.384)
90
(27.432)
100
(30.480)
1/4
(6.35)
.364
(9.246)
43
(1.13)
29
(.82)
24
(.68)
20
(.57)
18
(.51)
16
(.45)
15
(.42)
14
(.40)
13
(.37)
12
(.34)
3/8
(9.53)
.493
(12.522)
95
(2.69)
65
(1.84)
52
(1.47)
45
(1.27)
40
(1.13)
36
(1.02)
33
(.73)
31
(.88)
29
(.82)
27
(.76)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
1
(25.4)
1.049
(26.645)
680
(919.25)
465
(13.17)
375
(10.62)
320
(9.06)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
1–1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1–1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2
(50.8)
2.067
(52.502)
3950
(111.85)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
2–1/2
(63.5)
2.469
(67.713)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95)
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3
(76.2)
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
4
(101.6)
4.026
(102.260)
23000
(651.27)
15800
(447.39)
12800
(362.44)
10900
(308.64)
9700
(274.67)
8800
(249.18)
8100
(229.36)
7500
(212.37)
7200
(203.88)
6700
(189.72)
NOTE–Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.

Other manuals for Lennox G27M Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G27M Series and is the answer not in the manual?

Lennox G27M Series Specifications

General IconGeneral
BrandLennox
ModelG27M Series
CategoryFurnace
LanguageEnglish

Related product manuals