Sequence of Operation G32−5, −6
Sequence depends on type thermostat used. Units are
applicable for single stage or two stage thermostats.
Both type thermostats are described below. Thermo
stat jumper E20 dictates which mode unit will operate
in. See flow chart for more sequence detail.
SureLight Control Self Check
When there is a call for heat, the SureLight integrated con
trol runs a self check. The control checks for S10 primary
limit, S21 secondary limit (s) and S47 rollout switch nor
mally closed contacts. The control also checks for S102
high heat and S128 low heat prove switch (G32−75 only)
normally open contacts. Once self check is complete and
all safety switches are operational, heat call can continue.
Two−Stage Thermostat, Two Stage Heat. Jumper E20
set at TWO".
4− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
Pressure Switch mode.
G32−75 ONLY−SureLight control energizes combus
tion air inducer B6 on low heat speed. Combustion air
inducer runs until S128 prove switch contacts close
(switch must close within 2 1/2 minutes or control goes
into Watchguard Pressure Switch mode. Prove switch
S102 may also close). A 15 second pre−purge follows
once S128 closes.
5− SureLight control begins 20 second ignitor warm up
period.
6− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
7− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
8− After 45 second delay, indoor blower B3 is energized
on low heat speed.
The furnace will stay in this mode until first stage de
mand is satisfied OR a second stage heat demand is
initiated.
9− Second stage heat demand initiated. A 30 second sec
ond stage recognition period begins.
10− The combustion air inducer ramps up to high heat
speed.
G23−75 ONLY−S102 prove switch closes.
11− Gas valve energizes second stage heat.
12− B3 indoor blower ramps up to high heat speed.
Single−Stage Thermostat, Two Stage Heat. Jumper
E20 set at SINGLE"
1− SureLight control energizes combustion air inducer B6
on low heat speed. Combustion air inducer runs until
S102 prove switch contacts close (switch must close
within 2 1/2 minutes or control goes into Watchguard
Pressure Switch mode.
G32−75 ONLY−SureLight control energizes combus
tion air inducer B6 on low heat speed. Combustion air
inducer runs until S128 prove switch contacts close
(switch must close within 2 1/2 minutes or control goes
into Watchguard Pressure Switch mode. Prove switch
S102 may also close). A 15 second pre−purge follows
once S128 closes.
2− SureLight control begins 20 second ignitor warm up
period.
3− Gas valve opens on first stage for a 4 second trial for
ignition. Ignitor stays energized during the trial or until
flame sensed.
4− Flame is sensed, gas valve remains on first stage heat,
ignitor de−energizes.
5− After 45 second delay, indoor blower B3 is energized
on low heat speed.
6− A 10 minute (factory set) or 15 minute (field set) second
stage heat delay period begins.
7− The combustion air inducer ramps up to high heat
speed.
G32−75 ONLY−S102 prove switch closes.
8− Gas valve energizes second stage heat.
9− B3 indoor blower ramps up to high heat speed.

Other manuals for Lennox G32 SERIES

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox G32 SERIES and is the answer not in the manual?

Lennox G32 SERIES Specifications

General IconGeneral
BrandLennox
ModelG32 SERIES
CategoryFurnace
LanguageEnglish

Related product manuals