Page 29
TABLE 28
G32V−5, CCB1 and Two−Speed Outdoor Unit
OPERATING MODE SYSTEM DEMAND SYSTEM RESPONSE
System
Condition
Thermostat
Demand
*Relative Humidity
(EfficiencyPlus Lights)
****Compressor
Speed
Blower CFM
(COOL)
Comments
Normal o
eration
Y1 No demand. Acceptable Low
55% of
HIGH COOL
Compressor demand and indoor
blower s
eed controlled b
Y2 No demand. Acceptable High HIGH COOL
thermostat demand
Y1 No demand. Acceptable Low
55% of
HIGH COOL
Call for humidity
Y1
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
Low
55% of
HIGH COOL
Dehumidification mode does not begin
until after initial thermostat demand is
1st−stage cooling
demand
Demand
satisfied
Humidity level remains
slightly (1) above setpoint.
Demand continues.
Off
Off
satisfied and new cooling demand is
initiated.
Y1
Humidity level remains
slightly (1) above setpoint.
Demand continues.
High
**77%/74% of
HIGH COOL
Significant increase in
Y1
No demand. Acceptable
Low
55% of
HIGH COOL
If humidity rises significantly above set-
point, or if slide switch is moved signifi-
um
y
ur
ng
thermostat cooling
demand.
Y1
Humidity level rises signifi-
cantly (2 or more) above
setpoint. Demand initiated.
High
**77%/74% of
HIGH COOL
cantly, unit will immediately go into de-
humidification mode (in presence of
thermostat demand).
Y1
Humidity level
above setpoint.
High
**77%/74% of
HIGH COOL
When humidity demand is satisfied,
Humidity demand
satisfied durin
Y1
Humidity level falls below
setpoint. No demand.
High
HIGH COOL
blower immediately shifts to the COOL
CFM in order to hasten the end of the
cycle Unit can only shift out of high
thermostat demand.
None
No demand. Acceptable
Off
Off
cycle. Unit can only shift out of high
speed compressor operation at begin-
Y1
No demand. Acceptable
Low
55% of
HIGH COOL
ning of next cycle.
Y2
No demand. Acceptable
High
HIGH COOL
Call for humidity
removal during 2nd
stage thermostat
Y2
Humidity level rises slightly
(1) above setpoint. Demand
initiated.
High
**77%/74% of
HIGH COOL
Blower immediately changes speed in
response to thermostat demand.
eman
Y2
No demand. Acceptable
High
HIGH COOL
*Call for 1st stage
None
Humidity level is slightly (1)
above setpoint.
Off
Off
Dehumidification mode (high speed
compressor) begins with next thermo-
cooling a
ter call
or
humidity removal.
Y1
Humidity level is slightly (1)
above setpoint.
Low
55% of
HIGH COOL
stat demand after initial demand is sat-
isfied.
Call for 2nd stage
None
Humidity level is slightly (1)
above setpoint.
Off
Off
Reduced blower speed (dehumidifica-
tion speed) begins immediately with
cooling a
ter call
or
humidity removal
Y2
Humidity level is slightly (1)
above setpoint.
High
**77%/74% of
HIGH COOL
tion speed
begins immediately with
thermostat demand
Call for cooling after
None
Humidity level is significantly
above setpoint (2 or more).
Off
Off
If humidity increases significantly over
setpoint, or if slide switch is moved,
unit immediately goes into dehumidifi
signi
icant increase in
humidity
Y1 or Y2
Humidity level is significantly
above setpoint (2 or more).
High
**77%/74% of
HIGH COOL
unit immediately goes into dehumidifi-
cation mode (in presence of thermostat
demand).
Humidity demand
satisfied between
None
Humidity level is slightly (1)
above setpoint.
Off
Off
While unit is not operating (no thermo-
stat demand), slide switch is moved
down and back up Blower and com
thermostat demands
(unit off cycle).
Y1 or Y2
Humidity level falls below
setpoint. No demand.
High
HIGH COOL
down and back up. Blower and com-
pressor operate at high speed until
next thermostat demand.
Note − During mode of operation change from cooling to heating, indicating lights will not change until the first thermostat heating
demand.
*IMPORTANT - If power to unit is turned on with CCB1 calling for humidity removal, outdoor unit may be locked into high speed
indefinitely. To reset, move the humidity slide switch all the way down then back up to desired setpoint while the unit is running.
** Reduced blower speed is 77% of COOL for the V3 units; 74% of COOL for V5.
***If the two−speed control on a two−speed outdoor unit is set for LATCH 2 (15 minutes) or LATCH 3 (30 minutes), the compressor
will latch into high speed after a Y1 demand has occurred for that period of time.