Lennox G60UHV Series - Troubleshooting: Cooling Sequence of Operation

Lennox G60UHV Series
50 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
COOLINGSEQUENCEOF OPERATION
I
I
I POWER ON I
4,
IS POLARITY REVERSED?
I IS THERE NO
PROPER GROUND? 9
_ YES
THERMOSTAT CALLS FOR FIRST-STAGE COOL. I
4,
COMPRESSOR AND CONDENSER FAN
ENERGIZED.
4,
INDOOR BLOWER ENERGIZED ON FIRST STAGE
COOL SPEED AFTER 2 SECOND DELAY.
SIGNAL POLARITY REVERSED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION,
STATUS ERROR CODE 5 + 4.
SIGNAL IMPROPER GROUND AT LED.
CONTROL WILL CONTINUE TO CALL FOR COOLING
IN THIS CONDITION,
STATUS ERROR CODE 5 + 3.
4,
_1 FIRST-STAGE DEMAND FOR COOL SATISFIED?
I THERMOSTAT CALLS FOR SECOND-STAGE COOL,
4,
I ,NDOORBLOWERRAMPSUPTOSECOND-STAGECOOLSPEEDI
4,
ISECOND-STAGEDEMANDFORCOOLSAT'SF'ED?I
YES 4,
I
I_ COMPRESSOR AND CONDENSER FAN DE-ENERGIZED.
NDOOR BLOWER DE-ENEG ZED.
I