2 Check for the correct voltage at the furnace (furnace
operating).
3 − Check amp-draw on the blower motor.
Motor Nameplate__________Actual__________
NOTE − Do not secure the electrical conduit directly to the
air ducts or structure.
Blower Speeds
NOTE − CFM readings are taken external to unit with a dry
evaporator coil and without accessories.
1 − Turn off electrical power to furnace.
2 − Remove blower access panel.
3 − Disconnect existing speed tap at control board speed
terminal.
NOTE − Termination of any unused motor leads must be
insulated.
4 − Refer to blower speed selection chart on unit wiring dia-
gram for desired heating or cooling speed. See blower
performance data beginning on Page 48.
5 Connect selected speed tap at control board speed
terminal.
6 − Resecure blower access panel.
7 − Turn on electrical power to furnace.
Electronic Ignition
The integrated control has an added feature of an internal
Watchguard control. The feature serves as an automatic re-
set device for ignition control lockout caused by ignition fail-
ure. This type of lockout is usually due to low gas line pres-
sure. After one hour of continuous thermostat demand for
heat, the Watchguard will break and remake thermostat de-
mand to the furnace and automatically reset the control to
begin the ignition sequence.
Exhaust and Air Intake Pipe
1 − Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2 Are pressure switches closed? Obstructed exhaust
pipe will cause unit to shut off at pressure switches.
Check termination for blockages.
3 Reset manual flame rollout switches on burner box
cover.
Failure To Operate
If the unit fails to operate, check the following:
1 − Is the thermostat calling for heat?
2 − Are access panels securely in place?
3 − Is the main disconnect switch closed?
4 − Is there a blown fuse?
5 Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6 − Is gas turned on at the meter?
7 − Is the manual main shut-off valve open?
8 − Is the internal manual shut-off valve open?
9 Is the unit ignition system in lock out? If the unit locks out
again, inspect the unit for blockages.