15
WINTER OUTDOOR CONDITIONS
Indoor
Conditions
12ºC D
11ºC W
7ºC D
6ºC W
4ºC D
3ºC W
0ºC D
-1ºC W
-
4ºC D
-6ºC W
-7ºC D
-8ºC W
Capacity kW 3.01 2.73 2.47 1.76 1.65 1.58
15ºC
Input kW. 0.76 0.66 0.6 0.58 0.5 0.45
Capacity kW 2.86 2.64 2.34 1.69 1.53 1.41
18ºC
Input kW. 0.78 0.67 0.62 0.59 0.62 0.47
Capacity kW 2.77
2.3
2.22 1.62 1.59 1.33
20ºC
Input kW. 0.81
0.65
0.64 0.59 0.53 0.48
Capacity kW 2.61 2.23 2.13 1.58 1.26 1.17
22ºC
Input kW. 0.83 0.68 0.65 0.6 0.56 0.51
6.3GCM09N
SUMMER
OUTDOOR TEMPERATURE DRY
Indoor
Conditions
25ºC 30ºC 35ºC 40ºC 45ºC 50ºC
Total capacity kW 2.42 2.41 2.24 2.03 1.87 1.75
Sensitive capacity kW
1.72 1.69 1.65 1.53 1.43 1.36
21ºC D
15ºC W
Input kW. 0.72 0.75 0.8 0.84 0.89 0.97
Total capacity kW 0.65 2.55 2.45 2.24 2.11 1.98
Sensitive capacity kW
1.83 1.73 1.7 1.63 1.63 1.57
24ºC D
17ºC W
Input kW. 0.68 0.76 0.81 0.88 0.93 1.02
Total capacity kW 2.89 2.8
2.6
2.45 2.23 2.05
Sensitive capacity kW
1.99 1.95
1.81
1.78 1.66 1.63
27ºC D
19ºC W
Input kW. 0.65 0.78
0.82
0.92 0.96 1.03
Total capacity kW 3.03 2.98 2.92 2.83 2.69 2.46
Sensitive capacity kW
2.05 1.88 1.96 1.87 1.87 1.85
32ºC D
23ºC W
Input kW. 0.65 0.8 0.86 0.95 0.99 1.08

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox GCM07N and is the answer not in the manual?

Lennox GCM07N Specifications

General IconGeneral
BrandLennox
ModelGCM07N
CategoryAir Conditioner
LanguageEnglish

Related product manuals