EasyManuals Logo

Lennox GCS16-1853-235 User Manual

Lennox GCS16-1853-235
80 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #18 background imageLoading...
Page #18 background image
Page 18
PED16185 & PED16300
POWER EXHAUST FANS PERFORMANCE
Model No.
Air Volume
(cfm
Exhausted)
Return Air System
Static Pressure
(Inches Water Gauge)
4200 0
3800 .05
PED16 185
3500 .10
PED16185
3200 .15
2700 .20
2200 .25
6300 0
5750 .05
PED16300
5200 .10
4625 .15
4050 .20
CEILING DIFFUSER AIR THROW DATA
Air Volume
*Effective Throw Range (feet)
Model No.
Air Volume
(cfm)
RTD11
StepDown
FD11
Flush
3000 27  33 25  30
GCS16823
GCS16
953
3375 30  37 28  34
GCS16
953
3750 34  41 31  38
4400 34  42 32  40
GCS161353
4950 38  47 36  45
GCS 6 353
5500 43  52 40  50
4200 39  46 40  48
GCS161603
5000 41  50 43  52
GCS 6 603
5800 43  52 45  54
6000 45  55 48  55
GCS161853
6750 47  56 50  58
GCS 6 853
7500 49  58 55  66
GCS16 2553
8000 39  44 53  62
GCS162553
GCS162753
GCS16 3003
9000 47  56 55  64
GCS163003
10,000 49  58 57  67
*Throw is the horizontal or vertical distance an airstream travels on leaving the outletor
diffuser before the maximum velocity is reduced to 50 ft. per minute. Four sides open.
FIGURE 1
823/953 PARTS ARRANGEMENT
COMPRESSOR
AND CONTROL BOX ACCESS
CONDENSER COIL
FILTER SECTION
HEATING
CONTROLS
BURNERS
INDOOR BLOWER
COMBUSTION
AIR BLOWER
HEAT EXCHANGER
1st STAGE
COMPRESSOR
2nd STAGE
COMPRESSOR
1st STAGE EVAPORATOR
2nd STAGE EVAPORATOR
GAS VALVE
BLOWER ACCESS
CONDENSER
FAN

Questions and Answers: