SPECIFICATIONS GCS162553
Model No. GCS162553235 GCS162553470
Total Cooling Capacity (btuh) 210,000
*ARI
Total Unit Watts 21,400
360
EER (Btuh/Watts) 9.8
Ratings
Integrated Part Load Value 10.4
Refri
erant
22
Stage 1
Charge
Stage 2
18 lbs. 8 oz.
Blower wheel nominal diameter x width (in.) 20 x 18
Nominal motor horsepower 5
**Factory
Maximum usable horsepower 5.75
Evaporator
Installed
Drives
Voltage & phase 208/230v3ph or 460v3ph
ower
and
RPM range 660 840
Drive
Nominal motor horsepower 7.5
**Optional
Factor
Maximum usable horsepower 8.60
Installed
Voltage & phase 208/230v3ph or 460v3ph
Drives
RPM range 750 905
Net face area (sq. ft.) 21.0
Evaporator
Tube diameter (in.) & No. of rows 3/8 3
o
Fins per inch 13
Net face area (sq. ft.) 48.5
Condenser
Tube diameter (in.) & No. of rows 3/8 2
o
Fins per inch 20
Diameter (in.) & No. of blades (2) 26 4
Condenser
Air volume (cfm) 14,000 (Total)
Fans
Motor horsepower (2) 1
Motor watts 2100 (Total)
Btuh Input (low) 145,000 290,000
Btuh Output (low) 116,000 232,000
wo
age
Heating Capacity
Btuh Input (High) 235,000 470,000
(Natural Gas Only)
Btuh Output (High) 188,000 376,000
A.G.A. Thermal Efficiency 80% 80%
Btuh Input (low) 164,000 376,000
Btuh Output (low) 131,200 262,400
wo
age
Heating Capacity
Btuh Input (High) 235,000 470,000
(***LPG Gas Only)
Btuh Output (High) 188,000 328,000
A.G.A. Thermal Efficiency 80%
Gas Su
l
Natural
Connections fpt (in.)
***LPG
3/4 1
Recommended Gas
Natural 7
Supply Pressure (wc. in.)
***LPG 11
Condensate drain size mpt (in.) (2) 1
No. & size of filters (in.) (6) 20 x 25 x 2
Electrical characteristics 208/230v or 460v 60 hertz 3 phase
* Rated in accordance with ARI Standard 360; 95F outdoor air temperature and 80F db/67F wb entering evaporator air; minimum external duct static pressure.
**Using total air volume and system static pressure requirements determine from blower performance tables rpm and bhp required. Maximum usable hp of motors
furnished by Lennox are shown. If motors of comparable hp are used, be sure to keep within the service factor limitations outlined on the motor nameplate.
***For LPG units a field conversion kit is required and must be ordered extra. See Optional Accessories table.
208,000 Btuh and 9.6 EER at 208 volts.