EasyManuals Logo

Lennox GWB9 User Manual

Lennox GWB9
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25

Consideration for the following should be used when
6.
determining an appropriate location for termination of
combustion air and vent piping.
Comply with all clearances required as stated in paragraph •
7.
Termination should be positioned where vent vapors will •
not damage plants/shrubs or air conditioning equipment.
Termination should be positioned so that it will not be ef-•
fected by wind eddy, air born leaves, snow, or recirculated
ue gases.
Termination should be positioned where it will not be •
subjected to potential damage by foreign objects, such as
stones, balls, etc..
Termination should be positioned where vent vapors are •
not objectionable.
Put vent on a wall away from the prevailing winter wind. •
Locate or guard the vent to prevent accidental contact
with people or pets.
Terminate the vent above normal snowline. Avoid loca-•
tions where snow may dri and block the vent. Ice or
snow may cause the boiler to shut down if the vent be-
comes obstructed.
Under certain conditions, ue gas will condense, form-•
ing moisture, and may be corrosive. In such cases, steps
should be taken to prevent building materials at the vent
from being damaged by exhaust of ue gas.
e venting system shall terminate at least 3 feet above any
7.
forced air inlet (except the boiler’s combustion air inlet)
within 10 feet. e venting system shall terminate at least
12 inches from any air opening into any building. e
bottom of the vent shall be located at least 12 inches above
grade. Termination of the vent shall be not less than 7 feet
above an adjacent public walkway. e vent terminal shall
not be installed closer than 3 feet from the inside corner of
an L shaped structure. Termination of the vent should be
kept at least 3 feet away from vegetation. e venting sys-
tem shall terminate at least 4 feet horizontally from, and in
no case above or below, unless a 4 foot horizontal distance
is maintained, from electric meters, gas meters, regulators,
and relief equipment.


Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox GWB9 and is the answer not in the manual?

Lennox GWB9 Specifications

General IconGeneral
BrandLennox
ModelGWB9
CategoryBoiler
LanguageEnglish

Related product manuals