Application Guide INNOV@-0907- Page 17
interconnectivity systems
Basic Control µAC
Description
This combination allows the timed rotation of a unit in stand-by
within a group of maximum 6 units. If one of the connected units
generates an alarm, the stand-by unit will be activated.
Unit 1 Unit 2 Unit 3 Unit 6
STAND-BY UNIT
ATTENTION :
Please note that this is not a LAN.
Rotation time: 0 ÷ 250 hours.
• Master function:
Unit number 1 is dened as the master unit. This unit sends the
command to activate and deactivate the unit in stand-by.
(Unit 4 and 5)