Page 28
TABLE 7
ELECTRIC HEAT DATA LCA036(S)(H), LCA042(S)(H), LCA048(S)(H)
Electric Heat
*Heater Only
{{Total Unit (with Power Exhaust Fan) &
Electric Heat Minimum Circuit Ampacity
Required
& Net Weight
(Required)
Steps
Input
Input
Output
.75 hp
(.56 kW)
1.5 hp
(1.1 kW)
2 hp
(1.5 kW)
3 hp
(2.2 kW)
1 208 5.3 18,100 42 51
EHA060-7
1 220 5.9 20,100
1PH
208/230v - 1 ph (27L01)
1 230 6.4 21,900
47 56
1 240 7.0 23,900
}2 208 7.5 25,600 56 64
EHA060-10
}2 220 8.4 28,700
1PH
208/230v - 1 ph (27L02)
}2 230 9.2 31,400
63 72
}2 240 10.0 34,200
}2 208 11.3 38,600 78 87
EHA060-15
}2 220 12.6 43,000
1PH
208/230v - 1 ph (27L03)
}2 230 13.8 47,100
89 97
}2 240 15.0 51,200
}2 208 15.0 51,200 101 110
EHA060-20
}2 220 16.8 57,400
1PH
208/230v - 1 ph (27L04)
}2 230 18.4 62,800
115 123
}2 240 20.0 68,300
1 208 5.3 18,100 29 30 33 36
1 220 5.9 20,100
1 230 6.4 21,900
32 33 35 39
EHA060-7
1 240 7.0 23,900
208/230v - 3 ph (23L67)
EHAFB-7
1 440 5.9 20,100
3PH
1 460 6.4 21,900
16 16 17 19
1 480 7.0 23,900
1 550 5.9 20,100
1 575 6.4 21,900
13 14 14 15
1 600 7.0 23,900
1 208 7.5 25,600 37 38 40 44
1 220 8.4 28,700
1 230 9.2 31,400
41 42 44 48
EHA072-10
1 240 10.0 34,200
208/230v - 3 ph (23L68)
208/230v - 3 ph (27L07)
1 440 8.4 28,700
3PH
460v - 3 ph (27L13)
1 460 9.2 31,400
20 21 21 23
575v - 3 ph (27L18)
1 480 10.0 34,200
1 550 8.4 28,700
1 575 9.2 31,400
17 17 18 19
1 600 10.0 34,200
1 208 11.3 38,600 50 51 53 57
1 220 12.6 43,000
1 230 13.8 41,700
56 57 59 63
EHA072-15
1 240 15.0 51,200
208/230v - 3 ph (23L69)
EHAFB-15/20
1 440 12.6 43,000
3PH
460v - 3 ph (27L14)
1 460 13.8 47,100
28 28 29 31
EHAFB-15
1 480 15.0 51,200
1 550 12.6 43,000
1 575 13.8 47,100
23 23 24 25
1 600 15.0 51,200
}2 208 15.0 51,200 63 64 66 70
}2 220 16.8 57,400
}2 230 18.4 62,800
71 72 74 78
EHA072-20
}2 240 20.0 68,300
208/230v - 3 ph (23L70)
EHAFB-20/25
1 440 16.8 57,400
3PH
460v - 3 ph (27L15)
1 460 18.4 62,800
35 36 37 38
EHAFB-15/20
1 480 20.0 68,300
1 550 16.8 57,400
1 575 18.4 62,800
29 29 30 31
1 600 20.0 68,300
{Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements. Use wires suitable for at least 167°F (75°C).
}May be used with two stage control.
*NOTE — Heater Sub-Fuse Box is required for fusing electric heat and must be ordered extra. Factory installed heaters will have fuse box installed. Also requires LTB2 Terminal Block.