TABLE 5
036 NORMAL OPERATING PRESSURES - NO REHEAT - ALL-ALUMINUM COIL - 581061-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
114 232 116 271 118 314 120 361 122 412 124 468
123 235 125 274 127 317 130 364 132 415 134 471
142 241 145 280 148 323 150 370 153 422 156 477
163 247 166 286 169 330 173 377 176 429 179 484