LGT/LCT036, 048, 060, 072
TABLE 6
048 NORMAL OPERATING PRESSURES - NO REHEAT - ALL-ALUMINUM COIL - 581062-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
117 244 120 281 122 324 123 372 124 426 124 485
124 247 128 284 131 327 134 375 135 429 136 489
139 255 144 292 149 335 153 383 157 437 160 497
153 264 160 301 166 344 172 393 178 447 182 507
048 CHARGING CURVE - NO REHEAT - ALL-ALUMINUM COIL - 581062-01
Suction Pressure (psig)
70
80
90
100
110
120
110 120 130 140 150 160
Outdoor Temperature (°F)
170 180
105°
95°
115°
85°
75°
65°
60
130