Page 24
LGT/LCT036, 048, 060, 072
TABLE 7
060 NORMAL OPERATING PRESSURES - NO REHEAT - ALL-ALUMINUM COIL - 581063-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
112 245 114 283 116 327 117 379 120 429 122 487
120 249 123 288 125 331 127 380 130 433 132 491
139 259 142 297 145 341 147 389 150 444 152 505
156 270 162 312 167 355 170 403 173 456 175 516
060 CHARGING CURVE - NO REHEAT - ALL-ALUMINUM COIL - 581063-01
Suction Pressure (psig)
70
80
90
100
110
120
110 120 130 140 150 160
Outdoor Temperature (°F)
170 180
105°
95°
115°
85°
75°
65°
60
130