Page 25
LGT/LCT036, 048, 060, 072
TABLE 8
072 NORMAL OPERATING PRESSURES - NO REHEAT - ALL-ALUMINUM COIL - 581064-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
110 260 112 301 115 348 117 401 118 459 120 524
118 263 121 304 124 350 126 403 128 462 130 526
135 272 139 313 143 359 146 412 149 470 152 534
154 286 159 326 163 373 167 425 171 483 175 547
072 CHARGING CURVE - NO REHEAT - ALL-ALUMINUM COIL - 581064-01
Suction Pressure (psig)
70
80
90
100
110
120
105 115 125 135 145 155
Outdoor Temperature (°F)
165 175
105°
95°
115°
85°
75°
65°
60
130