LGT/LCT036, 048, 060, 072
TABLE 9
036 NORMAL OPERATING PRESSURES - REHEAT - ALL-ALUMINUM COIL - 581108-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
114 239 116 278 118 325 121 378 123 438 125 505
123 241 125 280 128 326 130 379 132 438 135 505
142 248 145 286 148 330 151 382 153 441 156 506
164 257 167 293 170 337 173 388 176 445 179 510
036 CHARGING CURVE - REHEAT - ALL-ALUMINUM COIL - 581108-01
Suction Pressure (psig)
70
80
90
100
110
120
110 120 130 140 150 160
Outdoor Temperature (°F)
170 180
105°
95°
115°
85°
75°
65°
60