Page 28
LGT/LCT036, 048, 060, 072
TABLE 11
060 NORMAL OPERATING PRESSURES - REHEAT - ALL-ALUMINUM COIL - 581110-01
Outdoor Coil Entering Air Temperature
65 F 75 F 85 F 95 F 105 F 115 F
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
Suct
(psig)
Disc
(psig)
109 254 111 293 112 337 114 387 116 442 118 502
118 259 120 298 122 342 124 392 126 447 128 508
137 270 139 309 142 354 145 403 147 458 150 519
158 283 161 322 164 366 167 416 170 471 173 531
060 CHARGING CURVE - REHEAT - ALL-ALUMINUM COIL - 581110-01
Suction Pressure (psig)
70
80
90
100
110
120
105 115 125 135 145 155
Outdoor Temperature (°F)
165 176
105°
95°
115°
85°
75°
65°
60
130