Page 43
LGT/LCT036, 048, 060, 072
FIGURE 35
ATTACH LIGHT ASSEMBLY
#8 SCREWS
UVC LIGHT
ASSEMBLY
Lamp Disposal
Hg-LAMP Contains Mercury.—Manage in accordance
with local, state and federal disposal laws. Refer to
www.lamprecycle.org or call 800-953-6669.
Proper Clean-up Technique in Case of Lamp
Breakage
Wear protective gloves, eye wear and mask.
Sweep the broken glass and debris into a plastic bag, seal
the bag, and dispose of properly. Contact your local waste
management office for proper disposal.
Do not use a vacuum cleaner. Do not incinerate.
Maintenance
For all maintenance, contact a qualified HVAC
technician.
Read the maintenance instructions before opening
unit panels.
Unintended use of the unit or damage to the unit
housing may result in the escape of dangerous UVC
radiation. UVC radiation may, even in small doses,
cause harm to the eyes and skin.
Do not operate units that are obviously damaged.
Do not discard the triangular UVC light shield or any
barriers with an ultraviolet radiation symbol.
Do not override the door interlock switch that
interrupts power to the UVC light.
Do not operate the UVC light outside of the unit.
L-Replacement Fuses
See the following tables for the proper replacement fuse
sizes.
Note:
LS = Low Static Blower Option
HS = High Static Blower Option
TABLE 15
REPLACEMENT FUSES
LGT036
Unit Voltage 208/230V - 1 Ph 208/230V - 3 Ph 460V - 3Ph 575V - 3Ph
Power Exhaust Option W / P.E. W / O P.E. W / P.E. W / O P.E. W / P.E. W / O P.E. W / P.E. W / O P.E.
Diagram
Key
Class
Blower
Type
Amps
F10
2
CC LS 8A 8A 8A 8A 8A 8A 8A 8A
F27 CC LS - - - - - - 7.5A 7.5A
F30 CC LS 10A 10A 10A 10A 5A 5A - -
F31 CC LS 15A 15A 15A 15A 15A 15A - -
F57 CC LS - - - - 3.5A 3.5A 5A 5A
F57 CC HS - - - - 10A 10A 7.5A 7.5A
F61
2
J LS 40A 35A 25A 25A 15A 15A 15A 15A
F61
2
J HS - - 25A 25A 15A 15A 15A 15A
CB10
3
- LS 40A 35A 25A 25A 15A 15A 15A 15A
CB10
3
- HS - - 25A 25A 15A 15A 15A 15A
2
Fuses F10 and F61 are only used on units with SCCR installed.
3
Units using Circuit Breakers will use CB10 option.