Page 45
LGT/LCT036, 048, 060, 072
LGT072
Unit Voltage 208/230V - 3 Ph 460V - 3Ph 575V - 3Ph
Power Exhaust Option W / P.E. W / O P.E. W / P.E. W / O P.E. W / P.E. W / O P.E.
Diagram
Key
Class Blower Type Amps
F10
2
CC HS 8A 8A 8A 8A 8A 8A
F27 CC HS - - - - 7.5A 7.5A
F30 CC HS 10A 10A 5A 5A - -
F31 CC HS - 15A 15A - -
F57 CC HS - - 10A 10A 7.5A 7.5A
F61
2
J HS 45A 45A 20A 20A 15A 15A
CB10
3
J HS 45A 45A 20A 20A 15A 15A
2
Fuses F10 and F61 are only used on units with SCCR installed.
3
Units using Circuit Breakers will use CB10 option.
LCT036
Electric Heat Size 7.5 KW 15 KW
Unit Voltage
208/230V
- 1 Ph
208/230V
- 3 Ph
460V -
3Ph
575V -
3Ph
208/230V
- 1 Ph
208/230V
- 3 Ph
460V -
3Ph
575V -
3Ph
Power Exhaust
Option
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
W /
P. E .
W / O
P. E .
Diagram
Key
Class
Blower
Type
Amps Amps
F3
RK or K
LS 40 40 25 25 15 15 15 15 40 40 50 50 25 25 20 20
F42
RK or K
LS - - - - - - - - 40 40 - - - - - -
F4
RK or K
1
LS 40 35 25 25 15 15 15 15 35 35 25 25 15 15 15 15
F4
RK or K
1
HS - - 25 25 15 15 15 15 - - 25 25 15 15 15 15
F10
2
CC
LS 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
F27
CC
HS - - - - - - 7.5 7.5 - - - - - - 7.5 7.5
F30
CC
LS 10 10 10 10 5 5 - - 10 10 10 10 5 5 - -
F31
CC
LS 15 15 15 15 15 15 - - 15 15 15 15 15 15 - -
F57
CC
LS - - - - 3.5 3.5 5 5 - - - - 3.5 3.5 5 5
F57
CC
HS - - - - 10 10 7.5 7.5 - - - - 10 10 7.5 7.5
F61
2
J
LS 50 45 35 30 20 15 20 15 90 90 60 60 30 30 25 25
F61
2
J
HS - - 35 30 20 15 15 15 - - 60 60 30 30 25 25
CB10
3
-
LS 50 45 35 30 20 15 20 15 90 90 60 60 30 30 25 25
CB10
3
-
HS - - 35 30 20 15 15 15 - - 60 60 30 30 25 25
1
When SCCR is installed, F4 fuse is Class J.
2
Fuses F10 and F61 are only used on units with SCCR installed.
3
Units using Circuit Breakers will use CB10 option.

Questions and Answers: