Page 6
ELECTRICAL DATA 4-5 TON
Model No. LCA/LGA048
Line voltage data 60 Hz
208/230v
1 phase
208/230v
3 phase
460v
3 phase
575v
3 phase
O
u
t
d
o
o
r
F
a
n
M
o
t
o
r
Full load amps 2.4 1.3 1.0
O
u
t
d
o
o
r
Fan Motor
Locked rotor amps 4.7 2.4 1.9
I
n
d
o
o
r
M
o
t
o
r
O
u
t
p
u
t
hp 0.75 1.5 0.75 1.5 2 3 0.75 1.5 2 3 0.75 1.5 2 3
Indoor
B
l
o
w
e
r
M
o
t
o
r
Output
kW 0.56 1.1 0.56 1.1 1.5 2.2 0.56 1.1 1.5 2.2 0.56 1.1 1.5 2.2
B
l
o
w
e
r
M
o
t
o
r
Full load amps 4.6 11.5 4.6 5.7 7.5 10.6 2.3 2.8 3.4 4.8 2.3 2.4 2.7 3.9
M
o
t
o
r
Locked rotor amps 10 55 10 40 46.9 66 5.4 20 20.4 26.8 5.4 15 16.2 23.4
O
p
t
i
o
n
a
l
P
o
w
e
r
Horsepower (W) 1/2 (363)
Optional Power
E
x
h
a
u
s
t
F
a
n
Full load amps 4.4 1.7
E
x
h
a
u
s
t
F
a
n
Locked rotor amps 4.7 4.1
Service Outlet (2) 115 volt GFCI (amp rating) 15
LCA/LGA048S MODELS
C
o
m
p
r
e
s
s
o
r
Rated load amps each 23.4 12.2 7.1 5.8
C
o
m
p
r
e
s
s
o
r
Locked rotor amps each 110.0 90.0 46.0 37.0
R
e
c
.
m
a
x
.
f
u
s
e
s
i
z
e
(
a
m
p
s
)
With Exhaust Fan 60 70 35 35 40 40 20 20 20 20 15 15 15 15
R
e
c
.
m
a
x
.
f
u
s
e
size (amps)
Less Exhaust Fan 60 60 30 35 35 40 20 20 20 20 15 15 15 15
*
M
i
n
i
m
u
m
C
i
r
c
u
i
t
A
m
p
a
c
i
t
y
With Exhaust Fan 41 48 27 28 30 33 15 15 16 17 13 13 13 14
*
M
i
n
i
m
u
m
Circuit Ampacity
Less Exhaust Fan 37 44 23 24 26 29 13 13 14 15 11 11 11 13
LCA/LGA048H MODELS
C
o
m
p
r
e
s
s
o
r
Rated load amps each 23.7 13.5 7.4 5.8
C
o
m
p
r
e
s
s
o
r
Locked rotor amps each 129.0 99.0 49.5 40.0
R
e
c
.
m
a
x
.
f
u
s
e
s
i
z
e
(
a
m
p
s
)
With Exhaust Fan 60 70 40 40 40 45 20 20 20 20 15 15 15 15
R
e
c
.
m
a
x
.
f
u
s
e
size (amps)
Less Exhaust Fan 60 60 35 35 40 40 20 20 20 20 15 15 15 15
*
M
i
n
i
m
u
m
C
i
r
c
u
i
t
A
m
p
a
c
i
t
y
With Exhaust Fan 42 48 29 30 32 35 15 16 16 18 13 13 13 14
*
M
i
n
i
m
u
m
Circuit Ampacity
Less Exhaust Fan 37 44 24 25 27 30 13 14 14 16 11 11 11 13
Model No. LCA/LGA060
Line voltage data 60 Hz
208/230v -
1 phase
208/230v
3 phase
460v
3 phase
575v
3 phase
O
u
t
d
o
o
r
F
a
n
M
o
t
o
r
Full load amps 2.4 1.3 1.0
O
u
t
d
o
o
r
Fan Motor
Locked rotor amps 4.7 2.4 1.9
I
n
d
o
o
r
M
o
t
o
r
O
u
t
p
u
t
hp 0.75 1.5 0.75 1.5 2 3 0.75 1.5 2 3 0.75 1.5 2 3
Indoor
B
l
o
w
e
r
M
o
t
o
r
Output
kW 0.56 1.1 0.56 1.1 1.5 2.2 0.56 1.1 1.5 2.2 0.56 1.1 1.5 2.2
B
l
o
w
e
r
M
o
t
o
r
Full load amps 4.6 11.5 4.6 5.7 7.5 10.6 2.3 2.8 3.4 4.8 2.3 2.4 2.7 3.9
M
o
t
o
r
Locked rotor amps 10 55 10 40 46.9 66 5.4 20 20.4 26.8 5.4 15 16.2 23.4
O
p
t
i
o
n
a
l
P
o
w
e
r
Horsepower (W) 1/2 (363)
Optional Power
E
x
h
a
u
s
t
F
a
n
Full load amps 4.4 1.7
E
x
h
a
u
s
t
F
a
n
Locked rotor amps 4.7 4.1
Service Outlet (2) 115 volt GFCI (amp rating) 15
LCA/LGA060S MODELS
C
o
m
p
r
e
s
s
o
r
Rated load amps each 26.9 16.7 8.6 6.0
C
o
m
p
r
e
s
s
o
r
Locked rotor amps each 141.0 110.0 55.0 44.0
R
e
c
.
m
a
x
.
f
u
s
e
s
i
z
e
(
a
m
p
s
)
With Exhaust Fan 70 70 45 50 50 50 20 25 25 25 15 15 15 20
R
e
c
.
m
a
x
.
f
u
s
e
size (amps)
Less Exhaust Fan 60 70 40 45 45 50 20 20 20 25 15 15 15 15
*
M
i
n
i
m
u
m
C
i
r
c
u
i
t
A
m
p
a
c
i
t
y
With Exhaust Fan 46 52 33 34 36 39 17 17 18 19 13 13 13 15
*
M
i
n
i
m
u
m
Circuit Ampacity
Less Exhaust Fan 41 48 28 29 31 34 15 15 16 17 11 11 12 13
LCA/LGA060H MODELS
C
o
m
p
r
e
s
s
o
r
Rated load amps each 28.8 17.3 9.0 7.1
C
o
m
p
r
e
s
s
o
r
Locked rotor amps each 169.0 123.0 62.0 50.0
R
e
c
.
m
a
x
.
f
u
s
e
s
i
z
e
(
a
m
p
s
)
With Exhaust Fan 70 70 50 50 50 50 25 25 25 25 20 20 20 20
R
e
c
.
m
a
x
.
f
u
s
e
size (amps)
Less Exhaust Fan 70 70 45 45 45 50 20 20 20 25 15 15 15 20
*
M
i
n
i
m
u
m
C
i
r
c
u
i
t
A
m
p
a
c
i
t
y
With Exhaust Fan 48 55 34 35 36 40 17 18 18 20 14 14 15 16
*
M
i
n
i
m
u
m
Circuit Ampacity
Less Exhaust Fan 44 50 29 30 32 35 15 16 16 18 13 13 13 14
*Refer to National or Canadian Electrical Code manual to determine wire, fuse and disconnect size requirements.
NOTE Extremes of operating range are plus and minus 10 % of line voltage.
NOTE Where current does not exceed 100 amps, HACR type circuit breaker may be used in place of fuse (U.S. only).