Page 31
Table 8. Alarm Codes
Event
Code
ActionDisplay Message
Event
Code
44 ALARM(44) GAS VALVE ON NO DEMAND GV1 UNIT OFF. GV1 POWER BUT NO DEMAND. CHECK GAS PRESS, GAS VALVE
45 ALARM(45) GAS VALVE ON NO DEMAND GV3 UNIT OFF. GV3 POWER BUT NO DEMAND. CHECK GAS PRESS, GAS VALVE
46 - 49 Reserved
50 ALARM(50) PRIMARY HEAT 1 LIMIT OPEN S10 HEAT SECT 1 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
51 ALARM(51) STRIKE 3 PRIMARY HEAT 1 LIMIT OPEN S10 HEAT SECT 1 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
52 ALARM(52) SECONDARY HEAT 1 LIMIT OPEN S21 HEAT SECT 1 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
53 ALARM(53) STRIKE 3 SECONDARY HEAT 1 LIMIT OPEN S21 HEAT SECT 1 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, FILTER, LIMIT, AND WIRING.
54 ALARM(54) HEAT 1 ROLL OUT OPEN HEAT SECT 1 CHECK GAS ROLL OUT S47
ALARM(54) HEAT 1 S15 LIMIT OPEN HEAT SECT 1 LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
55 ALARM(55) STRIKE 3 HEAT 1 ROLL OUT OPEN HEAT SECT 1 CHECK GAS ROLL OUT S47
ALARM(55) STRIKE 3 HEAT 1 S15 LIMIT OPEN HEAT SECT 1 LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
56 ALARM(56) HEAT 1 CAI SWITCH S18 HEAT SECT 1 CHECK COMBUSTION AIR MOTOR & PROOF SWITCH
57 ALARM(57) STRIKE 3 HEAT 1 CAI SWITCH S18 HEAT SECT 1 OFF CHECK COMBUSTION AIR MOTOR & PROOF SWITCH
58 ALARM(58) HEAT 1 NO PROOF GAS VALVE GV1 HEAT SECT 1 CHECK IGNITION CONTROL, FLAME PROOF, GV1, GAS SUPPLY
59 ALARM(59) STRIKE 3 NO PROOF GAS VALVE GV1 HEAT SECT 1 CHECK IGNITION CONTROL, FLAME PROOF, GV1, GAS SUPPLY
60 ALARM(60) PRIMARY HEAT 2 LIMIT OPEN S99 HEAT SECT 2 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
61 ALARM(61) STRIKE 3 PRIMARY HEAT 2 LIMIT OPEN S99 HEAT SECT 2 PRIMARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
62 ALARM(62) HEAT 2 LIMIT OPEN S100 HEAT SECT 2 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, LIMIT, AND WIRING.
63 ALARM(63) STRIKE 3 HEAT 2 LIMIT OPEN S100 HEAT SECT 2 SECONDARY HEAT LIMIT OPEN. CHECK AIR FLOW, FILTER, LIMIT, AND WIRING.
64 ALARM(64) HEAT 2 ROLLOUT OPEN S69 CHECK ROLLOUT SENSOR AND GAS
65 ALARM(65) STRIKE 3 ROLLOUT OPEN S69 CHECK ROLLOUT SENSOR AND GAS
66 ALARM(66) HEAT 2 CAI SWITCH S45 HEAT SECT 2 CHECK COMBUSTION AIR MOTOR & PROOF SWITCH
67 ALARM(67) STRIKE 3 HEAT 2 CAI SWITCH S45 HEAT SECT 2 OFF CHECK COMBUSTION AIR MOTOR & PROOF SWITCH
68 ALARM(68) HEAT 2 NO PROOF GAS VALVE GV3 HEAT SECT 2 CHECK IGNITION CONTROL, FLAME PROOF, GV3, GAS SUPPLY
69 ALARM(69) STRIKE 3 NO PROOF GAS VALVE GV3 HEAT SECT 2 CHECK IGNITION CONTROL, FLAME PROOF, GV3, GAS SUPPLY
70 - 72 Reserved
73 ALARM(73) NETWORK SENSOR ERROR CHECK WITH INTEGRATOR FOR REFRESH RATE, NETWORK STATUS LIGHTS AND WIRING
74 ALARM(74) ZONE SENSOR A2 CHECK ZONE SENSOR AND WIRING
75 ALARM(75) OUTDOOR TEMP SENSOR RT17 CHECK SENSOR AND WIRING
76 ALARM(76) CHECK 2 AMP FUSE HUMIDITY SENSOR A91 CHECK SENSOR AND WIRING
77 ALARM(77) DISCHARGE AIR TEMP SENSOR RT6 CHECK SENSOR AND WIRING
78 ALARM(78) RETURN AIR TEMP SENSOR RT16 CHECK SENSOR AND WIRING
79 ALARM(79) ADD-ON BOARD PROBLEM ADD-ON BRD PROBLEM, RESET TO CLEAR
80 ALARM(80) ADD-ON BOARD PROBLEM ADD-ON BRD PROBLEM
81 ALARM(81) REHEAT SETUP ERROR CHECK REHEAT SETTINGS
82 ALARM(82) CONTROLLER RESET NO ACTION NEEDED
83 ALARM(83) INCORRECT SETTINGS CHECK CONFIGURATION
84 Reserved
85 ALARM(85) INCORRECT HUMIDITROL SETTINGS CHECK HUMIDITROL SETTINGS
86 ALARM(86) CONFLICTING TSTAT INPUT CHECK TSTAT INPUTS FOR SIMULTANEOUS HEAT AND COOL AND WIRING
87 Reserved
88 ALARM(88) CONTROLLER PROBLEM INTERNAL CONTROLLER PROBLEM. RESET TO CLEAR.
89 Reserved