EasyManuals Logo

Lennox LGM102U User Manual

Lennox LGM102U
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #6 background imageLoading...
Page #6 background image
Page 6
SPECIFICATIONS GAS HEAT
Heat Input Type Standard Medium High
Number of Gas Heat Stages 2 2 2


  84,500 117,000 156,000
 130,000 180,000 240,000
  104,000 144,000 192,000
 15 - 45 30 - 60 40 - 70
 2150 2250 2600
󰀩 80% 80% 80%
   
 
  
 
HIGH ALTITUDE DERATE




Gas Heat
Type
Altitude
Feet
Gas Manifold Pressure
in. w.g.
Input Rate - Btuh
(Natural Gas or LPG/Propane)
Natural Gas LPG/Propane Gas First Stage Second Stage
 2001-4500   84,500 124,000
 2001-4500   117,000 172,000
 2001-4500   156,000 230,000

Other manuals for Lennox LGM102U

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox LGM102U and is the answer not in the manual?

Lennox LGM102U Specifications

General IconGeneral
BrandLennox
ModelLGM102U
CategoryAir Conditioner
LanguageEnglish

Related product manuals