STEP 4 - Calculate superheat value on suction valves(According to form )
Measured Suction Line Pressure = _______ PSIG
STEP 5 - Calculate subcooling value on liquid valves(According to form )
Measured Suction Line Temp. = ________ºF
Calculate superheat value = ________ºF
Measured liquid Line Pressure = _______ PSIG
Measured liquid Line Temp = ________ºF
Calculate subcooling value = ________ºF
8 10 12 14 16 18 20 2
40 101 97 93 89 86 82 78 7
42 105 101 97 93 89 86 82 7
44 110 105 101 97 93 89 86 8
46 114 110 105 101 97 93 89 8
48 118 114 110 105 101 97 93 8
50 123 118 114 110 105 101 97 9
52 128 123 118 114 110 105 101 9
54 133 128 123 118 114 110 105 10
56 138 133 128 123 118 114 110 10
58 143 138 133 128 123 118 114 11
60 148 143 138 133 128 123 118 11
62 153 148 143 138 133 128 123 11
64 159 153 148 143 138 133 128 12
66 164 159 153 148 143 138 133 12
68 170 164 159 153 148 143 138 13
70 176 170 164 159 153 148 143 13
8
72 182 176 170 164 159 153 148 143
R-410A REFRIGERAN CHART
℉
SUCTION GAGE PRESSURE (PSI)
SUCTIO
TEMP
℉
6 7 8 9 10 11 12 13
55 173 176 179 182 185 188 191 19
60 188 191 195 198 201 204 208 21
65 204 208 211 215 218 221 225 22
70 221 225 229 232 236 239 243 24
75 239 243 247 251 255 259 262 26
80 259 262 266 270 275 279 283 28
85 279 283 287 291 295 300 304 30
90 300 304 309 313 318 322 327 33
95 322 327 331 336 341 346 351 35
100 346 351 355 360 365 370 376 38
105 370 376 381 386 391 397 402 40
110 397 402 407 413 418 424 430 43
115 424 430 435 441 447 453 459 46
120 453 459 465 471 477 483 489 49
125 483 489 496 502 508 515 521 52
R-410A REFRIGERAN CHART
FINALSUBCOOLING(℉)
LIQUID GAGE PRESSURE (PSI)
SUCTIO
TEMP
(℉)
107℉
107℉
Note: If calculated subcooling value is lower than the design
subcooling value, please add refrigerant. Repeat the steps above.
Note:Make sure the superheat value of suction valve
should be above 12ºF, if the value is lower than this,
indoor TXV should be adjusted.If the temperature is
higher than 18ºF, we suggest to adjust indoor TXV.
Repeat the steps above.
(If to adjust TXV ,steps of
adjustment are shown on
separate sheet , and
repeat this step.)
Model
Design subcooling
24 36 48 60
10ºF 10ºF 8ºF 7ºF