6. INSTALLATION DETAILS
6.1 Torque wrench installation sheet
Outside diameter
Torque Additional tightening torque
mm Inch N.cm N.cm
6.35 1/4 1500 (153kgf.cm) 1600 (163kgf.cm)
9.52 3/8 2500 (255kgf.cm) 2600 (265kgf.cm)
12.7 1/2 3500 (357kgf.cm) 3600 (367kgf.cm)
16 5/8 4500 (459kgf.cm) 4700 (479kgf.cm)
19 3/4 6500 (663kgf.cm) 6700 (683kgf.cm)
6.2 Connecting the cables
The connecting power cord should be selected according to the following specifi cations:
Rated current of appliance (Amps) Nominal cross-sectional area (mm²)
>3 and 6 0.75
>6 and 10 1.0
>10 and 16 1.5
>16 and 25 2.5
The cable size and the current of the fuse or switch are determined by the maximum current indicated on the nameplate which is located
on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.