Page 33
5 -  Test capacitor. Replace as necessary. 
6 -   Inspect contactor contacts for pitting or burn marks. 
Replace as necessary. 
7 -   Check fan motor for worn bearings/bushings. 
Replace as necessary. 
8 -   Inspect and clean coils, if necessary and note any 
damage to coils or signs of leakage. 
Filters 
1 -   Internal lter kits containing lter rails for 1 in. thick 
lters  are  available.  Filters  are  not  provided  and 
must be eld supplied. A lter is required, whether 
installed in the unit, in the ductwork or behind a lter 
grill in the conditioned area. 
NOTE - If PCO is installed, an internal lter kit is not rec-
ommended. 
2 -   Filters  should  be  inspected  monthly.  Replace 
disposable lters or clean permanent-type lters as 
necessary. Dirty lters are the most common cause 
of inadequate heating or cooling performance. 
Replace existing  lter with  a lter of  like type  and 
size. DO NOT replace a permanent-type lter with 
a disposable lter. Install new/clean lters with the 
arrows on the side pointing in the direction of airow. 
Healthy Climate® Photocatalytic Oxidation (PCO) Air 
Purication Accessory (LRP16 Series Only)
1 -   The  Healthy  Climate®  PCO  cartridge  and  UVA 
lamp require annual replacement. An annual 
maintenance kit is available that includes the PCO 
cartridge and UVA lamp. More frequent replacement 
may be required in applications with heavier dust or 
dirt  loads  or  in  applications  where  a  lower  MERV 
lter is installed before the Healthy Climate® PCO 
cartridge. The eld supplied lter should be changed 
at least annually, or according to the manufacturers 
recommended replacement cycle. 
General System Test with System Operating 
1 -   Perform a general system test. Turn on the air 
conditioner to check operating functions such as 
the startup and shuto operation. Check for unusual 
noises or odors, and measure indoor/outdoor 
temperatures and system pressures as needed. 
Check the refrigerant charge per the charging 
sticker information on the unit. 
2 -   Refer  to  the  nameplate  to  determine  the  correct 
temperature rise for all gas units (GE / DF). 
3 -   Verify that system total static pressure and airow 
settings are within specic operating parameters. 
4 -  Verify correct temperature drop across indoor coil. 
POST START-UP CHECKLIST (GAS) 
After the control circuit has been energized and the heat-
ing section is operating, make the following checks: 
1 -   Use soap solution to check for gas leaks in the unit 
piping as well as the supply piping. 
2 -   Check the supply gas pressure. It must be within the 
limits shown on rating nameplate. Supply pressure 
should be checked with all gas appliances in the 
building at full re. At no time should the supply gas 
pressure exceed 10.5 inches w.c., nor drop below 
5.0 inches w.c. for natural gas units. For propane 
gas, supply gas pressure should not drop below 11 
inches w.c. If gas pressure is outside these limits, 
contact your gas supplier for corrective action. 
3 -   Check for correct manifold gas pressures. See 
Check and Adjust Manifold Pressure. 
4 -   Adjust  temperature  rise  to  the  range  specied  on 
the rating plate. 
Check and Adjust Manifold Pressure 
After line pressure has been checked and adjusted, check 
manifold pressure. Refer to gure 14 for location of man-
ifold pressure adjustment screw and pressure tap outlet.
MANIFOLD PRESSURE 
TEST TAP
REGULATOR 
ADJUSTMENT
(UNDER CAP)
FIGURE 14 
The gas valve is factory set and should not require adjust-
ment. See the table below for pressures. The gas valve 
should completely and immediately cycle o in the event 
of gas or power failure. The manual shut-o knob or switch 
can be used to immediately shut o gas supply.
Manifold Pressure " w.c.
 1st Stage Heat
Natural 2.0 ± 0.3
LP 5.6 ± 0.3
2nd Stage Heat
Natural 3.5 ± 0.3
LP 10.0 ± 0.5
 IMPORTANT
For  safety,  connect  a  shut-o  valve  between  the 
manometer  and  the  gas  tap  to  permit  shut  o  of  gas 
pressure to the manometer.
1 -   Connect a test gauge to the outlet pressure tap on 
the gas valve. Start the unit and allow ve minutes 
for the unit to reach steady state. 
2 -   While waiting for the unit to stabilize, notice the 
ame. The ame should be stable without ashback 
and  should  not  lift  from  the  burner  head.  Natural 
gas should burn blue. L.P. gas should burn mostly 
blue with some orange streaks.