Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 1106-E • 57 •
ALL UNITS – HIGH AMBIENT
Size
442V 452VE 502V 552VE 602V 652VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
53,5 53,5 52 52 52 52
Size
702V 752VE 803V 853VE 953V 1003VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
52,5 52,5 52,5 52,5 52 52
Size
1053V 1153VE 1254V 1354VE 1404V 1504VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
51,5 51,5 52 52 51,5 51,5

Other manuals for Lennox MCC Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Lennox MCC Series and is the answer not in the manual?

Lennox MCC Series Specifications

General IconGeneral
BrandLennox
ModelMCC Series
CategoryChiller
LanguageEnglish

Related product manuals