EasyManua.ls Logo

Lennox MCC Series

Lennox MCC Series
86 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 1106-E • 58 •
ALL UNITS – LOW NOISE
Size
402V 422VE 442V 452VE 502V
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
51 51 51 51 50,5
Size
552VE 602V 652VE 702V 752VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
50,5 50,5 50,5 50,5 50,5
Size
803V 853VE 953V 1003VE 1053V
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
50,5 50,5 50,5 50,5 49
Size
1153VE 1254V 1354VE 1404V 1504VE
Operating limits
Min. outlet water temperature
°C
5
Max. inlet water temperature
°C
20
Min. difference water inlet/outlet
°C
3
Max. difference water inlet/outlet
°C
8
Min. outside air temperature
°C
6
Min. outside air temperature (1)
°C
-15
Max. outside air temperature (2)
°C
49 50,5 50,5 49 49

Other manuals for Lennox MCC Series

Related product manuals