Installation - Operation - Maintenance manual (IOM) AIR COOLED CHILLERS & SPLIT UNITS - 1106-E • 59 •
ALL UNITS – STANDARD / LOW NOISE / HIGH AMBIENT
Size
442V 452VE 502V 552VE 602V 652VE
Operating limits for Evaporator
Water Test pressure
Bar 10
Refrigerant Test pressure
Bar 26,5
Water Max. operating pressure
Bar 6
Refrigerant Max. operating pressure
Bar 26,5
Water Min. flow
m3/h
8°C
T
Water Max. flow
m3/h 89,3 89,3 153,5 153,5 153,53 153,5
Operating limits for Pressure gauge control
Safety Cut of low pressure
Bar 0,7
Safety Interlocking of low pressure
Bar 2,2
Safety Cut of high pressure
Bar 26,5
Safety Interlocking of high pressure
Bar 20