Page 9
I-UNIT COMPONENTS
Unit components are shown in FIGURE 1. The gas valve, 
combustion air inducer and burners can be accessed by 
removing the access panel. Electrical components are in 
the control box (FIGURE 2) found in the blower section.
ELECTROSTATIC DISCHARGE (ESD)
Precautions and Procedures
 CAUTION
Electrostatic discharge can aect electronic 
components. Take precautions to neutralize 
electrostatic  charge  by  touching  your  hand 
and  tools  to  metal  prior  to  handling  the 
control.
A- Control Box
1. Control Transformer (T1)
A  transformer  located  in  the  control box  provides  power 
to the low voltage section of the unit. Transformers on all 
models  are  rated  40VA  with  a  120V  primary  and  a  24V 
secondary.
2. Door Interlock Switch (S51)
A door interlock switch rated 14A at 125VAC is wired in se-
ries with line voltage. When the inner blower access panel 
is removed the unit will shut down.
Control Box Components
Integrated Control
Door Interlock Switch
Transformer
FIGURE 2 
 WARNING
Shock hazard.
Disconnect power before servicing. Integrated 
control is not eld repairable. If control is inoperable, 
simply replace entire control. Can cause injury 
or death. Unsafe operation will result if repair is 
attempted.
3. Integrated Control (A92)
Units are equipped with a two-stage, variable speed inte-
grated control. The system consists of a ignition / blower 
control (FIGURE 3) with control pin designations in TABLE 
3, TABLE 4 and 4 and ignitor. The control and ignitor work 
in combination to ensure furnace ignition and ignitor dura-
bility. The control provides gas ignition, safety checks and 
indoor blower control with two-stage gas heating. The fur-
nace combustion air inducer, gas valve and indoor blower 
are controlled in response to various system inputs such 
as thermostat signal, pressure and limit switch signal and 
ame signal.
The furnace has a built-in, self-diagnostic capability. If a
system  problem  occurs,  a  fault  code  is  shown  by  a  red 
LED on the control. The control continuously monitors its 
own operation and the operation of the system. If a failure 
occurs,  the  LED  will  indicate  the  failure  code. The  ash 
codes are presented in TABLE 2.
Fault Code History Button
The control stores the last ve fault  codes in memory. A 
pushbutton  switch  is  located  on  the  control.  When  the 
pushbutton  switch  is  pressed  and  released,  the  control 
ashes the stored fault codes. The most recent fault code 
is  ashed  rst;  the  oldest  fault  code  is  ashed  last.  To 
clear the fault code history, press and hold the pushbutton 
switch in for more than 5 seconds before releasing.
Single Stage Thermostat Operation
The automatic heat  staging option  allows a  single stage 
thermostat to be used with two stage furnace models. To 
activate this option, move the jumper pin (see FIGURE 3) 
to desired setting (5 minutes or 10 minutes). The furnace 
will start on 1st stage heat and stay at 1st stage heat for 
the duration of the selected time before switching to 2nd 
stage heat. W1 on the integrated control must be connect-
ed to W1 on the thermostat.
High Heat State LED
A green LED is provided on the control board to indicate 
high heat state (see TABLE 1).
CFM LED
An amber LED is provided on the control board to display 
CFM. To determine what  CFM the motor  is delivering at 
any time, count the number of times the amber LED ash-
es. Each ash signies 100 CFM; count the ashes and 
multiply by 100 to determine the actual CFM delivered (for 
example:  5  ashes  x  100  =  500  CFM).
TABLE 1 
High Heat State Green LED
LED Status Description
LED O No demand for high heat
LED On High heat demand, operating normally
LED Flashing
High heat demand, high pressure
switch not closed